Article number: ENRGSKN-328

CableScan mini+ Kit for identifying fault locations and cable tracing - GC "Energoscan"

"CableScan Mini +" is a set of devices for identifying fault locations (LPF) of power cables of all types of insulation using modern non-burning methods. And also to determine the location of damage to the insulation itself and the insulating shells of cables and pipelines, to determine the routes of cables, pipes and other underground utilities.

CableScan Portable Kit Mini + is designed both for preliminary determination of the location of damage (DPL) of cables using non-burning methods (TDR, ARC, ICM, Decay), and for precise PDL using the acoustic (acoustic-electromagnetic) method. Using the locating kit included in CableScan Mini +, you can determine the routes of cables, pipes and other underground utilities. Using the induction method, it determines the location of damage to the insulation itself and the insulating shells of cables and pipelines.

The kit allows you to produce OMD of power cables with different types of insulation (oil-paper, cross-linked polyethylene, plastic insulation, etc.) and different types of damage (low- and high-resistance damage, breaks, short circuits, intermittent breakdowns, etc.).

The CableScan Mini+ instrument kit is compact and weighs less than 50 kg. No special transport is required to transport it; it can even fit in the trunk of a car.

Advantages

1. Portability - the kit can be transported by one specialist,
2. Compactness - the entire set can be transported in a passenger car, all-terrain vehicle, or snowmobile,
3. Work in hard-to-reach places - the kit can be used where a mobile laboratory cannot pass: tunnels, remote fields, reactor plants in large buildings, etc.,
4. Efficiency - the kit includes all modern methods for preliminary and accurate determination of fault locations in cable lines,
5. Versatility - each device in the kit is an independent device and can be used separately.

Possibilities

  1. Accurate cable OMF using the acoustic (acoustic-electromagnetic) method (up to 32 kV, up to 2 kJ).
  2. Testing cable insulation with voltage up to 36 kV.
  3. Testing of cable sheath with voltage up to 10 kV.
  4. Preliminary localization of the damage site using the following methods:
    - pulse reflectometry (TDR);
    - pulse-arc (ARC);
    - oscillatory current discharge (ICM)
    - oscillatory voltage discharge (DECAY) (optional).

The kit includes locating equipment with the following functionality:
- detection of underground communications: cable lines, including live ones, metal and non-metallic pipes, metal fittings.
- selection of cable from a bundle.
- detection of faults (cable lines and protective coating of pipelines).

Parameter Meaning
High-voltage pulse generator GVI-36 M
Output pulse voltage 0-32 kV
Output DC voltage 0-36 kV
Time of continuous operation in pulse mode at maximum voltage 30 min
Maximum pulse energy 1000/2000 J
Weight 25 kg
Supply voltage frequency 50 Hz 220±22 V
Connecting device IDD-40 M
Maximum amplitude of input pulses ?40 kV
Supply voltage frequency 50 Hz 220±22 V
Weight 18 kg
Connecting device DT-50M
Pulse input current ? 5 kA
Output voltage to meter 50 V
Connecting device DN-80M
Input (rectified) voltage from source, kV 70 kV
Output voltage to the measuring device, V 50 V
Reflectometer
Measuring distance range 200/51200 m
Shortening factor setting or measurement within 1.00-7.00

Probing signals of pulse reflectometry mode:

-amplitude

-duration

6.5 V (increased at least 22 V)

20ns to 25 µs
Gain range, dB From -12 to 60
Memory, number of reflectograms 500
Search kit CSL-10
Full range of acoustic channel, Hz 80-1500
Gain, dB 80
WMD error, m 0.1
Battery operating time, h 9
Operating temperature, °C from -10 to +40

TECHNICAL PARAMETERS OF LINE SEARCH KIT

Parameter Values
Locator receiver CST-L
Active frequency range 640 Hz, 1280 Hz, 8 kHz, 33 kHz, 82 kHz, 197 kHz
Passive frequencies power – 50/60 Hz, cathodic protection –100/120 Hz, radio – 4-24 kHz, combined (power and radio)
Gain of the measured signal up to 99 dB
Screen color LCD, resolution 320x240 pixels, diagonal size 95 mm
Terms of Use from -25оС to +60оС
Battery powered Li-ion 7, 4 V, 3 Ah
Charging voltage DC 8.4 V, 2 A
Supply voltage AC 100-240 DC, 50 / 60 Hz
Weight 2.0 kg
IP 65
dimensions 680 x 120 x 277 mm
Dual frequency positioning module (optional) L1+L5, horizontal positioning error - 3-5 m, distance measurement error - 30 cm
Generator CST-G
Output frequency 640 Hz, 1280 Hz, 8 kHz, 33 kHz, 82 kHz, 197 kHz
Power 15 W, 10 steps of adjustment
Screen LCD 320x240, display of selected frequency and output level on screen
Operating temperature range from -25оС to +60оС
Resistance matching automatic
Overcurrent and overvoltage protection automatic
Battery powered Li-ion 7, 4 V, 6 Ah
Charging voltage DC 8.4 V, 2 A
Supply voltage AC 100-240 DC, 50 / 60 Hz
Weight 2.3 kg
IP 65
dimensions 280 x 220 x 90 mm

Basic equipment

- GVI-36M - portable high-voltage pulse generator
- IDD-40M - connecting device for pulse-arc method
- Flight 305 - reflectometer
- CSL-10 - search kit in a case
- CST-15 - route-search kit in a case
- Cable kit
- Documentation set

Additional equipment

- DN-80M-voltage connecting device
- DT-50M-current connecting device

Guarantee period 1 год