CableScan mini portable kit for locating cable faults - GC "Energoscan"
CableScan-Mini is a set of devices for determining the location of fault (LP) of power cables of all types of insulation using modern non-burning methods.CableScan Portable Kit Mini is designed both for preliminary determination of the location of damage (DPL) of cables using non-burning methods (TDR, ARC, ICM, Decay), and for precise PDL using the acoustic (acoustic-electromagnetic) method. Most damage to cable lines is detected using non-burning methods.
The system allows you to produce OMF of power cables with different types of insulation (oil-paper, cross-linked polyethylene, plastic insulation, etc.) and different types of damage (low- and high-resistance damage, breaks, short circuits, intermittent breakdowns, etc.).
The CableScan Mini instrument set is compact and weighs no more than 50 kg. No special transport is required to transport it; it can even fit in the trunk of a car.
Advantages
1. Portability - the kit can be transported by one specialist,
2. Compactness - the entire set can be transported in a passenger car, all-terrain vehicle, or snowmobile,
3. Work in hard-to-reach places - the kit can be used where a mobile laboratory cannot pass: tunnels, remote fields, reactor plants in large buildings, etc.,
4. Efficiency - the kit includes all modern methods for preliminary and accurate determination of fault locations in cable lines,
5. Versatility - each device in the kit is an independent device and can be used separately.
Possibilities
- Accurate cable OMF using the acoustic (acoustic-electromagnetic) method (up to 32 kV, up to 2 kJ).
- Testing cable insulation with voltage up to 36 kV.
- Testing of cable sheath with voltage up to 10 kV.
- Preliminary localization of the damage site using the following methods:
- pulse reflectometry (TDR);
- pulse-arc (ARC);
- oscillatory current discharge (ICM)
- oscillatory voltage discharge (DECAY) (optional).
Parameter | Meaning |
High-voltage pulse generator GVI-36 M | |
Output pulse voltage | 0-32 kV |
Output DC voltage | 0-36 kV |
Time of continuous operation in pulse mode at maximum voltage | 30 min |
Maximum pulse energy | 1000/2000 J |
Weight | 25 kg |
Supply voltage frequency 50 Hz | 220±22 V |
Connecting device IDD-40 M | |
Maximum amplitude of input pulses | ?40 kV |
Supply voltage frequency 50 Hz | 220±22 V |
Weight | 18 kg |
Connecting device DT-50M | |
Pulse input current | ? 5 kA |
Output voltage to meter | 50 V |
Connecting device DN-80M | |
Input (rectified) voltage from source, kV | 70 kV |
Output voltage to the measuring device, V | 50 V |
Reflectometer | |
Measuring distance range | 200/51200 m |
Shortening factor setting or measurement within | 1.00-7.00 |
Probing signals of pulse reflectometry mode: -amplitude -duration | 6.5 V (increased at least 22 V) 20ns to 25 µs |
Gain range, dB | From -12 to 60 |
Memory, number of reflectograms | 500 |
Search kit CSL-10 | |
Full range of acoustic channel, Hz | 80-1500 |
Gain, dB | 80 |
WMD error, m | 0.1 |
Battery operating time, h | 9 |
Operating temperature, °C | from -10 to +40 |
Contents of delivery:
- GVI-36M - portable high-voltage pulse generator
- IDD-40M - connecting device for pulse-arc method
- Flight 305 - reflectometer
- CSL-10 - search kit in a case
- Cable kit
- Documentation set
Additional equipment
- DN-80M-voltage connecting device
- DT-50M-current connecting device
Become a dealer |