CAM-5 – IntelliSAW Medium Voltage Equipment Monitoring System - IntelliSAW
The CAM-5 central module, part of the IntelliSAW continuous monitoring system for medium voltage equipment, is designed for collecting, processing and visualizing dataThe IntelliSAW CAM™-5 is the central module of a medium voltage equipment monitoring system that provides continuous monitoring of live part temperature, partial discharge, ambient temperature and relative humidity. Such systems are needed to monitor the condition of critical power supply assets such as switchgear, medium voltage circuit breakers and busbar trunking.
The CAM™-5 unit can operate as a stand-alone monitoring device, or as a data acquisition and monitoring device with 9 IRM READERs with the ability to easily integrate into substation SCADA systems with standard communications.
Connectivity to CAM™-5:
• 12 Wireless passive temperature sensors (SAW)
• 4 radio interfaces with partial discharge detection
• 8 humidity and ambient temperature sensors
• The system can operate up to 10 CAM™-5 units simultaneously
• 6 configurable alarm outputs
Application:
Medium and low voltage switchgears Busbars Insulated busbars Ring main blocks | Transformers Generator circuit breakers on-load tap-changer Rectifiers Capacitor blocks |
Areas of use
Generation: hydroelectric power station CHP Renewable energy power plants Transmission and distribution Step-up substations Step-down substations Collector substations | Industry: Heavy industry Metallurgical and aluminum plants Production Petrochemistry Data Centers |
Equipment installation examples
A medium voltage switchgear cabinet is an example of an installation where the CAM™-5 is installed in the low voltage compartment while all other sensors are installed in the high voltage compartments.
Integration of several monitoring modules
Up to 9 Reader modules can be connected to the CAM™-5 module, allowing each module (CAM™-5 or Reader) to configure unique temperature, partial discharge and humidity display settings and alarm configurations. Data from all devices can be viewed in real time, saved to a local USB drive and transferred to the SCADA system using standard communication protocols. CAM™-5 modules can also be connected to a SCADA system, providing a scalable and fully integrated solution.
Temperature | |
Operating frequency | 425 to 443 MHz |
Number of Temperature Sensors (SAW) | from 0 to 12 |
Redundancy module | up to 4 redundant antennas |
RF transmit power | Pulse, -6 to 10 dBm |
RF Receiver Sensitivity | -86 dBm |
Stable HF reception frequency | ±700 Hz |
RF Polling Distance | up to 1.75 m to Mast and 2.5 m to TPD Air Interface |
HF polling time | ? 160 ms |
Partial discharges | |
Number of channels | 4 |
Sensor type | IntelliSAW TPD CAM Air Interfaces |
Method of measurement | Ultra High Frequency (UHF) |
Measurement frequency bands | • 300MHz (270 – 330 MHz) • 600MHz (550 – 650 MHz) • 1200MHz (1050 – 1400 MHz) |
Classification of measurements | • Self-noise level • SD - surface discharge (Tracking, Treeing, Corona) • PD – internal partial discharges |
Units | |
Measurement scale | nonlinear, with the ability to calibrate against a reference source |
Measurement sensitivity | 100 pC at peak discharge value, at 24 kV |
Polling time | 200 ms |
Calculated data | Maximum SD Maximum PD |
Trending Algorithms | • Fast averaging function (?) • Long averaging function (?) |
HUMIDITY / AMBIENT TEMPERATURE | |
Number of channels | up to 8 sensors connected via bus |
Sensor type | IntelliSAW IH-10 |
Measurement type | Relative humidity, ambient temperature |
Response time | 500 ms |
Alarm output channel | |
Contact type | Dry contact, form C relay |
Number of contacts | 6, NO/NC with common |
Rated voltage | 250 V AC/DC |
Continuous flow current | no more than 10 A |
Maximum current 4 s | 15 A |
Cutting power (AC) | 2500 VA |
Cutting power (DC) | 24V, 5A / 125V, 0.45A |
COMMUNICATION INTERFACE | |
With devices | RS485 |
Port | 2-wire (half duplex) plus common (optional) |
Bus baud rate | 1200 to 38400 baud (9600 default) |
Data transfer protocol | Modbus RTU Master |
Response time | 500 ms (typ.), Polling intervals 1 second (typ.) |
Supported devices | IntelliSAW IRM Readers (up to 10 devices; speed varies by baud rate) |
Option for SCADA | RS485 |
Port | 2-wire (half duplex) plus common (optional) |
Bus baud rate | from 1200 to 38400 baud (9600 default) |
Data transfer protocol | Modbus RTU Slave DNP 3 Outstation |
Response time | 500 ms (typ.), Polling intervals 1 second (typ.) |
Type | Ethernet (ETH-1 and optional ETH-2) |
Port | 10/100 BASE-T (RJ45 connector) |
Data transfer protocol | • Modbus TCP • DNP3 Outstation • IEC 61850 • SFTP, SSH • OPC UA |
Type | Ethernet (optional ETH-2 FIBER) |
Port | 100 BASE-FX of IEEE802.3u |
Wavelength | 1300nm |
Optical connector | Duplex LC connector |
Connector type | Multimode |
Fiber size | 62.5 / 125 µm |
Data transfer protocol | • Modbus TCP • DNP3 Outstation • IEC 61850 • wSFTP, SSH • OPC UA |
Type | Measurement Configuration (CNFG) |
Port | USB 2.0 Mini; Windows COM port with FTDI drivers, 115200 baud |
Data protocol | Proprietary IntelliSAW protocol |
Type | Extended Memory (USB) |
Port | USB 2.0 Type A Host |
Data store | CSV file format extension |
Micro SD | Factory only |
OPERATIONAL POWER | |
AC input | 100 to 250 V 50/60 Hz |
DC input | from 120 to 250 V |
Power consumption | 20 W |
DIMENSIONS AND WEIGHT | |
Display size | 5'' / 800 x 480 pixels |
Overall size | Case: 143.6 x 100.25 x 101.6 mm Panel: 153.4 x 110.2 x 3.14 mm |
Weight | 0.98 kg |
Degree of protection | Panel: IP62 Housing: IP20 |
terms of Use | from -20? up to +70? 10 – 95% relative humidity non-condensing Maximum altitude 5000 m |
The equipment is agreed upon with a technical specialist
CAM5B-000-AMFU
CAM5 base:
- No monitoring
- Alarm outputs - 6 channels. (NO/NC)
- Multi-unit device interface (RS485)
- Communication interface: fiber optic (100 base FX)
- Standard communication: Modbus TCP
- Universal input power (100 to 250 VAC; 120 to 250 VDC)
CAM5B-TPH-AMSU
CAM5 base:
- Monitoring: temperature, partial discharge, ambient temperature and humidity
- Alarm outputs - 6 channels. (NO/NC)
- Multi-unit device interface (RS485)
- Communication interface: RS485 SCADA
- Standard communication: Modbus TCP
- Universal input power (100 to 250 VAC; 120 to 250 VDC)
CAM5B-TPH-AMEU
CAM5 base:
- Monitoring: temperature, partial discharge, ambient temperature and humidity
- Alarm outputs - 6 channels. (NO/NC)
- Multi-unit device interface (RS485)
- Communication interface: Ethernet
- Standard communication: Modbus TCP
- Universal input power (100 to 250 VAC; 120 to 250 VDC)
CAM5B-TPH-AMFU
CAM5 base:
- Monitoring: temperature, partial discharge, ambient temperature and humidity
- Alarm outputs - 6 channels. (NO / NC)
- Multi-unit device interface (RS485)
- Communication interface: fiber optic (100 base FX)
- Standard communication: Modbus
- Universal input power (100 to 250 VAC; 120 to 250 VDC)
CAM-5 Option
CAM5-INTP-DNP3 - Interface protocol – DNP3
CAM5-INTP-61850 - Interface protocol – IEC 61850
Guarantee period 1 год