The CAM-5 central module, part of the IntelliSAW continuous monitoring system for medium voltage equipment, is designed for collecting, processing and visualizing data

The IntelliSAW CAM™-5 is the central module of a medium voltage equipment monitoring system that provides continuous monitoring of live part temperature, partial discharge, ambient temperature and relative humidity. Such systems are needed to monitor the condition of critical power supply assets such as switchgear, medium voltage circuit breakers and busbar trunking.

The CAM™-5 unit can operate as a stand-alone monitoring device, or as a data acquisition and monitoring device with 9 IRM READERs with the ability to easily integrate into substation SCADA systems with standard communications.

Connectivity to CAM™-5:

• 12 Wireless passive temperature sensors (SAW)

• 4 radio interfaces with partial discharge detection

• 8 humidity and ambient temperature sensors

• The system can operate up to 10 CAM™-5 units simultaneously

• 6 configurable alarm outputs

Application:

Medium and low voltage switchgears

Busbars

Insulated busbars

Ring main blocks

Transformers

Generator circuit breakers

on-load tap-changer

Rectifiers

Capacitor blocks

Areas of use

Generation:

hydroelectric power station

CHP

Renewable energy power plants

Transmission and distribution

Step-up substations

Step-down substations

Collector substations

Industry:

Heavy industry

Metallurgical and aluminum plants

Production

Petrochemistry

Data Centers

Equipment installation examples

A medium voltage switchgear cabinet is an example of an installation where the CAM™-5 is installed in the low voltage compartment while all other sensors are installed in the high voltage compartments.

Integration of several monitoring modules

Up to 9 Reader modules can be connected to the CAM™-5 module, allowing each module (CAM™-5 or Reader) to configure unique temperature, partial discharge and humidity display settings and alarm configurations. Data from all devices can be viewed in real time, saved to a local USB drive and transferred to the SCADA system using standard communication protocols. CAM™-5 modules can also be connected to a SCADA system, providing a scalable and fully integrated solution.

Temperature

Operating frequency

425 to 443 MHz

Number of Temperature Sensors (SAW)

from 0 to 12

Redundancy module

up to 4 redundant antennas

RF transmit power

Pulse, -6 to 10 dBm

RF Receiver Sensitivity

-86 dBm

Stable HF reception frequency

±700 Hz

RF Polling Distance

up to 1.75 m to Mast and 2.5 m to TPD Air Interface

HF polling time

? 160 ms

Partial discharges

Number of channels

4

Sensor type

IntelliSAW TPD CAM Air Interfaces

Method of measurement

Ultra High Frequency (UHF)

Measurement frequency bands

• 300MHz (270 – 330 MHz)

• 600MHz (550 – 650 MHz)

• 1200MHz (1050 – 1400 MHz)

Classification of measurements

• Self-noise level

• SD - surface discharge

(Tracking, Treeing, Corona)

• PD – internal partial discharges

Units

Measurement scale

nonlinear, with the ability to calibrate against a reference source

Measurement sensitivity

100 pC at peak discharge value, at 24 kV

Polling time

200 ms

Calculated data

Maximum SD

Maximum PD

Trending Algorithms

• Fast averaging function (?)

• Long averaging function (?)

HUMIDITY / AMBIENT TEMPERATURE

Number of channels

up to 8 sensors connected via bus

Sensor type

IntelliSAW IH-10

Measurement type

Relative humidity, ambient temperature

Response time

500 ms

Alarm output channel

Contact type

Dry contact, form C relay

Number of contacts

6, NO/NC with common

Rated voltage

250 V AC/DC

Continuous flow current

no more than 10 A

Maximum current 4 s

15 A

Cutting power (AC)

2500 VA

Cutting power (DC)

24V, 5A / 125V, 0.45A

COMMUNICATION INTERFACE

With devices

RS485

Port

2-wire (half duplex) plus common (optional)

Bus baud rate

1200 to 38400 baud (9600 default)

Data transfer protocol

Modbus RTU Master

Response time

500 ms (typ.), Polling intervals 1 second (typ.)

Supported devices

IntelliSAW IRM Readers (up to 10 devices; speed varies by baud rate)

Option for SCADA

RS485

Port

2-wire (half duplex) plus common (optional)

Bus baud rate

from 1200 to 38400 baud (9600 default)

Data transfer protocol

Modbus RTU Slave

DNP 3 Outstation

Response time

500 ms (typ.), Polling intervals 1 second (typ.)

Type

Ethernet (ETH-1 and optional ETH-2)

Port

10/100 BASE-T (RJ45 connector)

Data transfer protocol

• Modbus TCP • DNP3 Outstation • IEC 61850 • SFTP, SSH • OPC UA

Type

Ethernet (optional ETH-2 FIBER)

Port

100 BASE-FX of IEEE802.3u

Wavelength

1300nm

Optical connector

Duplex LC connector

Connector type

Multimode

Fiber size

62.5 / 125 µm

Data transfer protocol

• Modbus TCP • DNP3 Outstation • IEC 61850 • wSFTP, SSH • OPC UA

Type

Measurement Configuration (CNFG)

Port

USB 2.0 Mini; Windows COM port with FTDI drivers, 115200 baud

Data protocol

Proprietary IntelliSAW protocol

Type

Extended Memory (USB)

Port

USB 2.0 Type A Host

Data store

CSV file format extension

Micro SD

Factory only

OPERATIONAL POWER

AC input

100 to 250 V 50/60 Hz

DC input

from 120 to 250 V

Power consumption

20 W

DIMENSIONS AND WEIGHT

Display size

5'' / 800 x 480 pixels

Overall size

Case: 143.6 x 100.25 x 101.6 mm

Panel: 153.4 x 110.2 x 3.14 mm

Weight

0.98 kg

Degree of protection

Panel: IP62

Housing: IP20

terms of Use

from -20? up to +70?

10 – 95% relative humidity non-condensing

Maximum altitude 5000 m

The equipment is agreed upon with a technical specialist

CAM5B-000-AMFU

CAM5 base:

- No monitoring

- Alarm outputs - 6 channels. (NO/NC)

- Multi-unit device interface (RS485)

- Communication interface: fiber optic (100 base FX)

- Standard communication: Modbus TCP

- Universal input power (100 to 250 VAC; 120 to 250 VDC)

CAM5B-TPH-AMSU

CAM5 base:

- Monitoring: temperature, partial discharge, ambient temperature and humidity

- Alarm outputs - 6 channels. (NO/NC)

- Multi-unit device interface (RS485)

- Communication interface: RS485 SCADA

- Standard communication: Modbus TCP

- Universal input power (100 to 250 VAC; 120 to 250 VDC)

CAM5B-TPH-AMEU

CAM5 base:

- Monitoring: temperature, partial discharge, ambient temperature and humidity

- Alarm outputs - 6 channels. (NO/NC)

- Multi-unit device interface (RS485)

- Communication interface: Ethernet

- Standard communication: Modbus TCP

- Universal input power (100 to 250 VAC; 120 to 250 VDC)

CAM5B-TPH-AMFU

CAM5 base:

- Monitoring: temperature, partial discharge, ambient temperature and humidity

- Alarm outputs - 6 channels. (NO / NC)

- Multi-unit device interface (RS485)

- Communication interface: fiber optic (100 base FX)

- Standard communication: Modbus

- Universal input power (100 to 250 VAC; 120 to 250 VDC)

CAM-5 Option

CAM5-INTP-DNP3 - Interface protocol – DNP3

CAM5-INTP-61850 - Interface protocol – IEC 61850

Guarantee period 1 год