as@emakgroup.ae

Working hours of the company:

MON - FRI: from 9:00 to 18:00

Order a call
Close
Article number: ENRGSKN-12

CBA-2000 High Voltage Circuit Breaker Tester - I.S.A. - Altanova group

System for monitoring the basic parameters of medium and high voltage class circuit breakers. Tests oil, gas and vacuum circuit breakers in three-phase mode with six breaks per phase. The ability to install a microohmmeter into the device eliminates the need to use a separate device.

The CBA-2000 installation is designed to monitor the condition of medium and high voltage class circuit breakers. The installation allows you to check the following parameters of the switch:

  • timing characteristics of main and auxiliary contacts,
  • currents of electromagnets on and off,
  • speed parameters and contact travel parameters,
  • contact resistance in static and dynamic modes,
  • tripping of the switch at low voltage.

The unit can test oil, SF6 and vacuum circuit breakers.

Using an additional option, timing characteristics can be measured on a switch grounded on both sides, which makes work much safer for the operator and the device itself.

The CBA-2000 unit operates on battery power and mains power. It has a large LCD display on which you can evaluate and analyze the results. Test results are saved in the internal memory of the device. The device can work without connecting to a computer or with it, using free specialized TDMS software. The results can be printed on the built-in or internal printer.

TDMS software allows you to pre-define a test plan, analyze test results and generate a protocol. The program is compatible with all ISA test rigs. The circuit solutions used in the CBA2000 are designed for safe and reliable operation in harsh electromagnetic environments of medium and high voltage substations and power plants.

The CBA-2000 device in its basic configuration weighs only 13 kg, and with a built-in microohmmeter - 15 kg. Can be supplied in a shock-resistant plastic case at the request of the customer.


Functional features:

  • Possibility of monitoring up to 18 main contacts or contacts with shunt resistors
  • Possibility to control up to 12 auxiliary contacts
  • Built-in microohmmeter 200A
  • Built-in memory
  • Large LCD display
  • Analysis of results on display
  • Checking switches with double-sided grounding
  • Possibility of connecting a SF6 gas sensor or linear/angular movement
  • Free software

Electromagnet control

Number of channels 2 channels (control of one trip electromagnet and one closing electromagnet) or 4 channels as an option (control of three trip electromagnets and one closing electromagnet)
Maximum voltage 300V DC / 300V AC
Maximum current 30A DC / 20A AC
Time measurement error 50 µs
Electromagnet current measurement range 2.5A, 10A,25A
Current measurement error 0.5% of measured value and ±0.1% of range

Control of main contacts

Quantity 6 / 12 /18 main contacts (2 / 4 / 6 breaks per phase) with the ability to check shunt resistances
Shunt resistor resistance range 25Ohm - 10 kOhm
Test voltage 24 V
Test current 50 mA

Auxiliary contact monitoring

Quantity 4 / 8 / 12 auxiliary contacts
Test voltage dry contact 24V, contact 20-300V
Test current

2 mA

Sampling frequency 20kHz - 10kHz - 5kHz - 2kHz - 1kHz - 500Hz - 200Hz - 100Hz, 50Hz and 20Hz - user selectable
Time measurement error 100 µs ± 0.025% of span at 20 kHz
Recording duration 1000 s

Analog inputs

Quantity 8 (2/4 for measuring currents of on and off coils; 1 for measuring resistance in static and dynamic mode, 3 for monitoring stroke and speed)
Input voltage range ±5V ±5V, ±50V, ±500V
Measurement resolution

16 bit

Digital inputs

Quantity 3
Type RS232
Input frequency

50 kHz

Nutrition 5V / 12V

Programmable test sequences

On and off cycles Disable;Enable;Disable - Enable;Enable - Disable; Disable - Enable - Disable; User defined.

Resistance measurement in static and dynamic modes (optional)

Test current (DC) 200 A, 100A or 20A
Contact resistance measurement range 1 mOhm, 10 mOhm or 100 mOhm selectable
Permission 1 µOhm, 10 µOhm, 100 µOhm
Error 1% of measured value
±0.2% of range

Checking the minimum operating voltage

Threshold voltage 250 V max. and 70 V max.
Maximum current 4 A(250 V); 10 A (70 V)
Maximum adjustable voltage up to 50% of nominal

External or internal printer (optional)

Interior thermal printer with ribbon (ribbon width 58 mm)
External SEIKO DPV-414, 112 mm
Graphic display Viewing area 122 x 92 mm

Control

Local With multi-function rotary button and keyboard (12 keys)
Via PC Via software, when connected to a PC
Software TDMS
PC communication interfaces Two communication interfaces: USB and RS232

Memory

Inner memory 128 MB or 250 results
External memory USB Flash Card

Nutrition

External power 85-265 V at a frequency of 50-60 Hz
100-350 VDC
Internal power Built-in battery, NiMh

Weight and dimensions

Weight 13 kg / 15 kg (with microohmmeter option)
dimensions 490 mm (H) x 370 mm (W) x 240 mm (D)
Standard equipment of CBA-2000:
  • Device CBA-2000
  • Set of cables in a bag
  • Network cable
  • RS-232 cable
  • USB cable
  • Spare fuses
  • TDMS Software
  • Plastic case
  • Manual
  • Warranty card of Energoscan Group of Companies

Additional equipment:

  • Built-in static/dynamic resistance measurement module 200 A
  • Checking the minimum operating voltage.
  • Internal printer
  • BSG1000 – external double-sided grounding module
  • Linear motion sensors
  • Angle sensors
  • Transport case
  • Universal sensor installation kit
  • External printer

Guarantee period 1 год