CBA-3000 High Voltage Circuit Breaker Tester - I.S.A. - Altanova group
A universal system that allows you to carry out a full range of tests of any type of circuit breaker (oil, SF6, air) medium and high voltage in a minimum time with maximum safety and accuracy. The device has a built-in three-phase microohmmeter. A special algorithm allows you to minimize the number of circuit breaker operations when conducting a comprehensive test.The CBA-3000 high-voltage circuit breaker testing system manufactured by ISA (Altanova Group) is designed to monitor the condition of medium and high voltage circuit breakers. The unit can test oil, SF6 and vacuum circuit breakers.
The device allows you to test any type of high-voltage circuit breaker with the following tests:
- measurement of timing characteristics of main contacts, pre-connected resistors and auxiliary contacts;
- measurement of speed parameters and contact travel parameters with the connection of sensors;
- minimum response voltage test;
- measuring the parameters of a switch grounded on both sides;
- measuring the time of the first shutdown;
- performance testing in complex cycles.
- measurement of currents and voltages of on and off electromagnets;
- measurement of contact resistance in static and dynamic modes in three-phase mode
The ability to check all parameters of the switch automatically in one connection allows you to significantly speed up the time of checking the switch.
Device features:
- Control of up to 24 main contacts/pre-connected resistors/auxiliary contacts;
- Resistance measurement of 3/6/9 contacts in static and dynamic modes with current up to 200 A;
- Large color display;
- 3 analog and 3 digital inputs for connecting displacement sensors;
- 8 analog inputs for measuring battery voltage, solenoid current, pressure, etc.
Electromagnet control
Number of channels | 2 / 4 / 6 channels of control of electromagnets on and off |
Maximum voltage | 300 V (DC) / 300 V (AC) |
Maximum current | 60 A (DC) / 42 A (AC) |
Time measurement error | 0.025% of shutter speed ± 20 µs |
Electromagnet current measurement range | 3 A, 10 A, 60 A |
Current measurement error | 0.1% of measured value and ±0.1% of range |
Contact control
Quantity | 16 / 24 contacts (main, pre-connected resistors, auxiliary contacts) |
Shunt resistor resistance range | 30 Ohm - 10 kOhm |
Test voltage | 24 V |
Test current | 100 mA |
Auxiliary contact monitoring
Test voltage | dry contact 24V (5 mA) floating contact, threshold 15 V / 77 V, or adjustable in 5 V steps |
Measuring time | |
Sampling frequency | 10 Hz – 100 kHz |
Permission | 0.01 ms – 100 ms |
Time measurement error
Range, s | frequency Hz | Resolution, ms | Error, % of measured value |
1 | 100000 | 0.01 | ±0.01ms ±0.01% |
2 | 50000 | 0.02 | ±0.02ms ±0.01% |
4 | 20000 | 0.05 | ±0.05ms ±0.01% |
10 | 10000 | 0.1 | ±0.1ms ±0.01% |
20 | 5000 | 0.2 | ±0.2ms ±0.01% |
40 | 2000 | 0.5 | ±0.5ms ±0.01% |
100 | 1000 | 1 | ±1ms ±0.01% |
Analog inputs
Quantity | 8 (fully controlled) |
Input voltage range | ± 1 V ± 10 V, ± 300 V AC, 420 DC |
Measurement resolution | 16 bit |
Digital inputs
Quantity | 3 |
Type | RS422 |
Input frequency | 50 kHz |
Programmable test sequences
On and off cycles | Disable; Turn on; Disable - Enable; Enable - Disable; Disable - Enable - Disable, User defined. |
Resistance measurement in static and dynamic modes (optional)
Test current (DC) | 200A, 150A, 100A, 50A, 25A |
Contact resistance measurement range | 250 μΩ, 1 mΩ, 10 mΩ, 50 mΩ, 500 mΩ |
Resolution (minimum) | 0.1 µOhm |
Error | 0.2% of change. meaning ± 0.2% of range (range: 250μOhm and 1mOhm) 0.3% of change meaning ± 0.3% of range (range: 10mOhm, 50mOhm and 500mOhm) |
Checking the minimum operating voltage
Threshold voltage | 250 V max. / 70 V max. (specified when ordering) |
Maximum current | 4 A(250 V); 10 A (70 V) |
External or internal printer (optional)
Interior | thermal printer with ribbon (ribbon width 58 mm) |
External | thermal printer with ribbon (ribbon width 112 mm) |
Control
Graphic display | Viewing area 152 x 92 mm, resolution (800 x 480), color LCD |
Local | With multi-function rotary button, function keys, keyboard (12 keys) |
Via PC | Via software, when connected to a PC |
Software | TDMS |
PC communication interfaces | Two communication interfaces: USB (for connecting a USB flash drive) and Ethernet |
Memory
Inner memory | 256 MB or 1000 results |
External memory | USB Flash Card |
Nutrition
External power | 85-265 V at 47-63 Hz 120-350 VDC |
Weight and dimensions
Weight | 15 kg (with microohmmeter option) |
dimensions | 407 mm (H) x 450 mm (W) x 230 mm (D) |
Standard equipment of CBA-3000:
- Installation of CBA-3000 (in various configurations, see description)
- Set of cables in a case
- Network cable
- Ground cable
- Ethernet cable
- USB cable
- Spare fuses
- TDMS Software
- Plastic case
- Manual
- Warranty card of Energoscan Group of Companies
Additional equipment
- IEC 61850-8 protocol
- Checking the minimum operating voltage
- Internal printer
- External printer
- BSG1000 – external double-sided grounding module
- Linear motion sensors
- Angle sensors
- Pressure meter
- Clamp meter
- Transport case
- Universal sensor installation kit
Guarantee period 1 год