as@emakgroup.ae

Working hours of the company:

MON - FRI: from 9:00 to 18:00

Order a call
Close
Article number: ENRGSKN-237

DRTS 33 Device for testing all types of relay protection devices - I.S.A. - Altanova group

The testing complex is designed to test all types of relay protection devices of all generations, from electromechanical and semiconductor to microprocessor-based with support for the IEC 61850 protocol. The device also allows you to test electricity meters, converters and power quality meters.

DRTS-33 - a relay protection test complex manufactured by ISA (Italy) is designed to test devices of all types of relay protection of all generations, from electromechanical and semiconductor to microprocessor-based with support for the IEC 61850 protocol. Also, the DRTS 33 ISA device can test electricity meters, converters and power quality meters.

The DRTS-33 device is equipped with 3 high power current sources (up to 32A) (up to 430 VA), and parallel connection will allow you to deliver a current of up to 96 A with a power of up to 1000 VA.

The device has a large color display and controls built into it, allowing you to carry out a range of tests without the need to connect a PC. By connecting to a PC, the full functionality of UAZiA checks using the TDMS software package becomes available. The set of programs is entirely in Russian, allowing you to check protection both manually and automatically, using special programs. The ability to save test results and plans allows you to simplify re-testing of protections or new testing of standard protections in the future.

List of programs:

  • Manual control
  • MTZ (50-51)
  • Directional MTZ (67/67 N)
  • Distance protection (21) (with the ability to use RIO and XRIO files)
  • Synchronism control relay (25)
  • Excitation loss protection (40)
  • Swing lock (68)
  • Asynchronous mode protection (78)
  • Relay protection and automation test plans editor
  • Advanced editor of test plans for relay protection and automation
  • Test sequencer
  • Playback and recording of emergency processes recorded by digital oscillograms (Comtrade)
  • Checking electricity meters
  • Checking converters
  • Checking power quality meters
  • Power system model

Additionally, the DRTS/33 ISA device can be equipped with a current amplifier for 6 currents (6x32A), an internal/external GPS synchronizer, an external storage device, a module for working with IEC 61850-8 and IEC 61850-9 protocols, a system for testing electric meters SHA-6 additional cables and various transport cases.

Functional features of DRTS-3 3:

  • Output current: 3 x 32 A (3 x 420VA), 1 x 96 A (1 x 1000 VA)
  • Output voltage, 3 x 300 V (4 x 85 VA), 1 x 600 V (1 x 200 VA)
  • Frequency range of current and voltage channels from 0 to 3000 Hz
  • Phase angle adjustment range from 0° to 360°
  • Output DC voltage: 0...260 V.
  • Interface types: USB, Ethernet, IRIG-B
  • Inner memory
  • Ability to work without a computer
  • IEC 61850 protocol support
  • Universal TDMS Software
  • Large color display
  • Compact size and light weight

DRTS33 Specifications:

Output currents

Current outputs (range):

3 x 0..32 A/1 x 0 … 96 A/1 x 0 …85 A DC

Current output power

3 x 420 VA/1 x 1000 VA/1 x 750 VA DC

Accuracy of current outputs:

Accuracy of current outputs:

±(0.04% of reading + 0.01% of range) – guaranteed

Output voltage

Voltage outputs (range):

3 x 0…300 V/1 x 0…600 V

Voltage output power:

3 x 100 VA / 1 x 200 VA

Voltage output accuracy:

±(0.04% of reading + 0.01% of range) – guaranteed

Common to current and voltage outputs

Frequency range (current):

0 … 3000 Hz

Frequency range (voltage):

0 … 3000 Hz

Frequency range of transient signals

0 … 5000 Hz

Phase angle setting range

0°…+360°

Permission:

0.001°

Auxiliary power supply

Auxiliary auxiliary power supply

0-260 V (DC voltage) / 50 W

Digital inputs

Digital inputs (quantity)

12

Contact options

dry"; live (AC, DC)

Sampling frequency

10 kHz

Permission

0.01 ms

Pulse counters (quantity)

2

Maximum sample rate

100 kHz

Digital outputs

Discrete outputs (relay)

4

Switching voltage range

300 V AC (2400 VA) / 300 V DC (50 W)

Discrete outputs (transistor)

4 (option 87170)

AC/DC measuring inputs

Quantity

10 (option 82170)

Voltage range

600 V

Error

0.15% (max)

Sampling frequency

up to 50 kHz

Input impedance

500 kOhm // 50 pF

Measured parameters and functions

Current with clamp meter (AC + DC), Voltage (AC + DC), Phase angle, Frequency, Power, Oscilloscope, Recorder, Recording waveforms in memory.

Low Level Inputs

Number of outputs

6 (option 87170)

Setting range

0…12.5 Vpk

Max. exit current

5mA

Accuracy

0.015% of measured value 0.05%

Communication and control interfaces

Communication interfaces:

Ethernet, USB, USB for connecting a flash card, IRIG B

Color LCD display

256 colors, resolution 320x240 pixels, diagonal 5.7 inches.

Internal memory of the device

256 MB /2000 results

Controlling the device using a PC with installed software

There is

Dimensions and weight

Weight

18 kg

Size

466 x 150 x 423 mm

Basic equipment DTRS 33:

  • Relay protection test system DRTS 33
  • Soft protective bag;
  • Set of test cables;
  • Power cable;
  • Grounding cable;
  • USB and Ethernet cables
  • Manual
  • Warranty card of Energoscan Group of Companies
  • Certificate of initial verification

Additional equipment DRTS 33:

  • Output expansion module and synchronization input via IRIG-B (code 87170)
  • Internal GPS receiver with antenna (cable length 20 m)* (code 88170)
  • External GPS receiver with antenna and cable (code 10161)
  • IEC61850-9 protocol module – Sampled Values* (code 89170)
  • IEC61850-8 protocol module – Goose (code 83170)
  • Step-down current transformer HPB 400 (for testing electromechanical protection) (code ZII70170)
  • Step-down current transformer HPB 600 (for testing electromechanical protection) (code ZII71170)
  • Step-down current transformer IN2-CDG (for testing electromechanical protection) (code 98156)
  • TRANSCOPE analog signal oscillography, recording and measurement module (option 82170)
  • Hall effect clamp meter
  • Universal scanning head SH-2003 for checking electricity meters (code 20162)
  • Additional set of test cables and accessories for connection to protections (code 15170)
  • Plastic transport case (dust- and moisture-proof) (code 85170)
  • Aluminum transport case (code 17170)
  • Soft transport bag (optional) (code 18170)
  • Synchronization device with the mains supply (code 72170)
  • Stand (for vertical installation of the DRTS system (code 19170)
  • Polarity check module (code 41175)
  • Laptop with bag

External amplifiers for DRTS 33:

  • AMI/332 – 3 additional current sources (3x32A) (code 80170)
  • AMI/632 – 6 additional current sources (6x32A) (code 8170)

Guarantee period 1 год

Leave a request

Leave a request and our manager will contact you within an hour
callback
1
$settings->wid3get_name}
Emak Group

What can we offer you