DRTS 64 Device for testing all types of relay protection devices - I.S.A. - Altanova group
The DRTS 64 testing complex is designed to test all types of relay protection devices of all generations - from electromechanical and semiconductor to microprocessor-based with support for the IEC 61850 protocol. The device allows you to test electricity meters, converters and power quality meters.DRTS-64 is a relay protection test complex manufactured by ISA (Italy), designed to test all types of relay protection of all generations, from electromechanical and semiconductor to microprocessor-based with support for the IEC 61850 protocol. The device can test electricity meters, converters and power quality meters.
DRTS-64 is equipped with six high power current sources (up to 32A) (up to 430 VA), and parallel connection will provide a current of up to 128 A and a power of up to 1000 VA.
The device has a large color display and controls for testing without the need to connect to a PC. After connecting the device to the computer, the full functionality of UAZiA checks using the TDMS software package becomes available. The software package is entirely in Russian. Special programs allow you to check protection in manual and automatic modes. The ability to save test results and plans simplifies re-testing of protections and new testing of type protections.
The DRTS-64 ISA device can be equipped with a current amplifier for 3 currents (3x32A), a current amplifier for 6 currents (6x32A), an internal/external GPS synchronizer, an external storage device, a module for working with IEC 61850-8 and IEC 61850-9 protocols, system for testing electric meters SHA-6 with additional cables and various transport cases.
List of programs:
- Manual control
- MTZ (50-51)
- Directional MTZ (67/67 N)
- Distance protection (21) (with the ability to use RIO and XRIO files)
- Differential protection of line and transformers (87)
- Synchronism control relay (25)
- Excitation loss protection (40)
- Swing lock (68)
- Asynchronous mode protection (78)
- Relay protection and automation test plan editor
- Advanced editor of test plans for relay protection and automation
- Test sequencer
- Playback and recording of emergency processes recorded by digital oscillograms (Comtrade)
- Checking electricity meters
- Checking converters
- Checking power quality meters
- Power system model
Functional features of DRTS-64:
- Output current: 6 x 32 A (3 x 420VA), 3 x 64 A (3 x 860 VA), 1 x 128 A (1 x 1000 VA)
- Output voltage, 4 x 300 V (4 x 85 VA), 1 x 600 V (1 x 200 VA)
- Frequency range of current and voltage channels from 0 to 3000 Hz
- Phase angle adjustment range from 0° to 360°
- Output DC voltage: 0...260 V.
- Interface types: USB, Ethernet, IRIG-B
- Inner memory
- Ability to work without a computer
- IEC 61850 protocol support
- Universal TDMS Software
- Large color display
- Compact size and light weight
Additional equipment DRTS-64:
- Output expansion module and synchronization input via IRIG-B (code 87170)
- Internal GPS receiver with antenna (cable length 20 m)* (code 88170)
- External GPS receiver with antenna and cable (code 10161)
- IEC61850-9 protocol module – Sampled Values* (code 89170)
- IEC61850-8 protocol module – Goose (code 83170)
- Step-down current transformer HPB 400 (for testing electromechanical protection) (code ZII70170)
- Step-down current transformer HPB 600 (for testing electromechanical protection) (code ZII71170)
- Step-down current transformer IN2-CDG (for testing electromechanical protection) (code 98156)
- TRANSCOPE analog signal oscillography, recording and measurement module (option 82170)
- Hall effect clamp meter
- Universal scanning head SH-2003 for checking electricity meters (code 20162)
- Additional set of test cables and accessories for connection to protections (code 15170)
- Plastic transport case (dust- and moisture-proof) (code 85170)
- Aluminum transport case (code 17170)
- Soft transport bag (optional) (code 18170)
- Synchronization device with the mains supply (code 72170)
- Stand (for vertical installation of the DRTS system (code 19170)
- Polarity check module (code 41175)
- Laptop with bag
External amplifiers for DRTS 64:
- AMI/332 – 3 additional current sources (3x32A) (code 80170)
- AMI/632 – 6 additional current sources (6x32A) (code 8170)
Output currents
Current outputs (range) | 6 x 0..32 A /3 x 0...64 A /1 x 0...128 A /1 x 0...85 A DC |
Current output power | 6 x 430 VA / 3 x 860 VA / 1 x 1000 VA / 1 x 750 VA DC |
Current output error | ± (0.04% of reading + 0.01% of range) – guaranteed |
Output voltage
Voltage outputs (range) | 4 x 0…300 V/ 3 x 0…300 V/1 x 0…600 V |
Voltage output power | 4 x 85 VA / 3 x 100 VA / 1 x 200 VA |
Voltage Output Accuracy | ± (0.04% of reading + 0.01% of range) – guaranteed |
Common to current and voltage outputs
Frequency range (current) | 0 … 3000 Hz |
Frequency range (voltage) | 0 … 3000 Hz |
Frequency range of transient signals | 0 … 5000 Hz IP30 with cover open |
Phase angle setting range | 0°…+360° |
Permission | 0.001° |
Auxiliary power supply
Auxiliary auxiliary power supply | 0 - 260 V (constant voltage) / 50 W |
Digital inputs
Digital inputs (quantity) | 12 |
Contact options | dry"; live (AC, DC) |
Frequency range of transient signals | 0 … 5000 Hz IP30 with cover open |
Sampling frequency | 10 kHz |
Permission | 0.01 ms |
Pulse counters (quantity) | 2 |
Maximum sample rate | 100 kHz |
Digital outputs
Discrete outputs (relay) | 4 |
Switching voltage range | 300 V AC (2400 VA) / 300 V DC (50 W) |
Discrete outputs (transistor) | 4 (option 87170) |
AC/DC measuring inputs
Quantity | 10 (option 82170) |
Voltage range | 600 V |
Error | 0.15% (max) |
Sampling frequency | up to 50 kHz |
Input impedance | 500 kOhm // 50 pF |
Measured parameters and functions | Current with clamp meter (AC + DC), Voltage (AC + DC), Phase angle, Frequency, Power, Oscilloscope, Recorder, Waveform recording in memory |
Low Level Inputs
Number of outputs | 6 (option 87170) |
Setting range | 0…12.5 Vpk |
Max. exit current | 5mA |
Accuracy | 0.015% of measured value 0.05% |
Communication and control interfaces
Communication Interfaces | Ethernet, USB, USB for connecting a flash card, IRIG B |
Color LCD display | 256 colors, resolution 320x240 pixels, diagonal 5.7 inches |
Internal memory of the device | 256 MB /2000 results |
Controlling the device using a PC with installed software | Eat |
Dimensions and weight
Weight | 20 kg |
Size | 466 x 150 x 423 mm |
- Relay protection test complex DRTS-64
- Soft protective bag;
- Set of test cables;
- Power cable;
- Grounding cable;
- USB and Ethernet cables
- Manual
- Warranty card of Energoscan Group of Companies
- Certificate of initial verification
Additional equipment DRTS-64
Specified in the description
Guarantee period 1 год