DTL C Automatic Transformer Oil Tester - BAUR
The DTL C unit is used to measure the dielectric constant and loss tangent and electrical resistivity of insulating oils.Automatic transformer oil tester DTL C is used to measure dielectric constant and dissipation tangent and electrical resistivity of insulating oils. Dissipation tangent tan δ and dielectric constant εr along with breakdown strength are the most important parameters of insulating oils.
Basic DTL C measurements :
- Loss tangent (tan δ)
- Dielectric constant (εr)
- Electrical resistivity in Ohm*m
- All known test sequences, such as IEC 247, VDE 0370, BS 148, ASTM 924, GOST 6581, etc., are programmed as standard sequences.
Functional features of DTLC :
- automatic calibration of empty measuring cell
- measurement of electrical resistivity from 2.5 MOhm to 20 TOmm, voltage up to 500 V DC of any polarity (optional - up to 100 TOmm)
- tan δ measurement from 110-5 to 4.0 (400%)
- measurement of dielectric constant εr
- HF induction heating element: short heating time and uniform heating
- easy to use equipment; measurement of loss tangent and electrical resistivity is carried out automatically in accordance with a given standard or with individually selected parameters
- direct temperature measurement using a sensor inside the measuring electrode
- built-in RS 232 interface for communication with PC
Technical characteristics of DTL C:
DC test voltage | Adjustable in the range from 500 to 2000 V (rms value), stability ± 100? 10-6 when the mains voltage changes ± 10% | |
AC measurements | Peak value/√2, accuracy ±1% | |
DC test voltage | Adjustable from 125 to 500 V | |
DC measurements | Accuracy ±0.5% | |
Test frequency | 50 or 60 Hz (selectable) | |
Dielectric constant (εr) | Range 1.0 to 10.0, accuracy ± 1% of measured value | |
Electrical resistivity measurement | Range from 2.5 MΩ to 20 TΩ (optional up to 100 TΩ) | |
Rho+/Rho- | (1 ohm = 100 ohm-cm) | |
Temperature measurement | Range from 5 to 120° C, error 0.4%, resolution 0.1° C Adjustment of the set value from 11 to 110? C | |
Measuring time according to IEC247 standard | Cycle time approximately 25 minutes. for tan 5, εr and ± Rho (including charge and discharge times) | |
Selectable standard programs | EC 247/VDE 0380, part 2 (1996) | VDE 0380 |
VDE 0370, part (1978) | ASTM D 924-96 (100°C) | |
VDE 0371, part (1980) | BS 148-1972 VDE 0374 | |
VDE 0374 | AS 1767-1975 | |
VDE 0375, part (1995) | JIS C2101-1978 | |
Customer-specified parameters | ||
Model capacitor | SF6 capacitor filled with compressed gas, 115 pF, tan δ < 1 ?10-5 | |
Element constant K (metric) | equals 0.113 pF? empty element capacity | |
Measuring the loss tangent tanδ | Max. resolution 1? 10-5; resolution range: 4095 digits in 3 decades, automatic adjustment from | |
0.00001 to 0.04095 | ||
from 0.0409 to 0.4095 | ||
from 0.409 to 4.095 (= 400%) | ||
error: ± 1% of measured value + 0.00008 | ||
Display | 2 x 40 digits, alphanumeric LCD with cursor functions | |
Printer | 24-pin matrix with ink ribbon, width 57 mm | |
Interface for pairing with external equipment | RS 232 (V 24), 2400 bps, 8 bits, no parity, DP25 connector | |
Selectable options: | ||
Test number | 24 digits | |
Test frequency | 50 or 60 Hz | |
Initial measurement temperature | ? 10°C | |
Temperature step size | ? 1°C | |
Temperature at the end of the test | Max. 110°C | |
AC Test Voltage | 500... 2000 V (rms value Vrms) | |
DC test voltage | ± 125 ... ± 500 V | |
Heater | HF induction method, | |
heating time for element: max. 16 min. from 25° to 90° C | ||
Storage temperature | from - 20 to + 50° C | |
Operating temperature range | from 0 to 40° C | |
Relative humidity | Max. 95% (no condensation) | |
Power supply | can be selected, 110 - 120 V /220 - 230 V / 240 V; 50 to 60 Hz | |
Energy consumption | 300 VA | |
Batteries | 3 pcs, 1.5 V (IEC R6) for data, clock and date memory, service life approx. 4 years | |
Dimensions of the measuring bridge, with dust cover | approximately. 450? 460? 500 mm | |
Dimensions of the measuring bridge, in wooden transport packaging | approximately 540? 480? 580 mm | |
Weight (including element) | 32 kg | |
Package weight | 40 kg |
Basic equipment:
- DTL C tester
- Cover to protect DTL from dust
- Drain tube for measuring cell, 1.5 m
- Measuring cell MC 2A with carrying case
- Syringe, 50 ml
- Temperature sensor for measuring cell
- Power cord
- Operating manual in Russian.
Additional equipment:
- Transport case for DTL
- Measuring cell MC 2A including transport case
- BAUR ITS software for device control from a PC, results processing and archiving.
- Printer ribbon
- Printer paper roll, width 57mm, diameter 30mm
Guarantee period 1 год