e-KAM Primary Current Test System - I.S.A. - Altanova group
Designed for fully automatic testing of relay protection devices, circuit breakers and current transformers with a primary current of up to 7000 A during maintenance of substation and electrical networks. Testing is automated as much as possible to speed up the testing process and reduce possible errors.The primary current testing system produced by ISA (Italy) is designed to load primary and secondary equipment with primary current up to 7000 A.
The device consists of a control unit and a load transformer. This separation allows you to install or raise the load transformer directly to the test object, reducing the length of the test cables and, accordingly, the load.
Depending on the required output current, three load transformer models are available: BUX 2000 (2000 A), BUX 3000 (3000 A) and BUX 5000 (5000 A, 7000 A max.).
The control unit is equipped with a large color display, UBS, Ethernet communication interfaces and a port for connecting a USB flash card.
Together with additional options, the system allows you to measure grounding resistance, soil resistivity, step voltage and touch voltage
Peculiarities
- Fully automatic system
- Large display and internal memory
- Three versions of load transformers
- Modular system: control unit and load transformer
- IEC 61850-9-2 protocol for CT testing.
Metrological characteristics of inputs
Entrance | Range | Error ± meas. meaning ± range |
Alternating current | 1 A; 10 A | < %0.05 < %0.05 |
Direct current | 1 A; 10 A | < %0.03 < % 0.08 |
High voltage AC | 300 mV; 3 V; 30 V; 300 V | < %0.15 < %0.05 < %0.05 < %0.05 |
Low voltage AC | 30 mV 300 mV 3 V | < %0.1 < %0.25 < %0.08 < %0.08 < %0.03 < %0.08 |
Constant voltage | 10 mV; 100 mV 1 V; 10 V | < %0.08 < %0.08 < %0.03 < %0.08 |
Stopwatch | Input type: NO, NC. "dry" or potential (300 V) Resolution: 1ms Range: up to 9999 Accuracy: ±0.001% meas. meaning ± 0.1 ms | |
Phase angle | Range: 0-360° Resolution: 0.01° Accuracy: <0.15° | |
Display | ||
Type | TFT LCD Color | |
Permission | 640 x 480 | |
Display size | 132 x 99 mm | |
Communication Interfaces | ||
Ethernet | Eat | |
USB for PC connection | Eat | |
USB for connecting a USB flash drive | 2 pcs | |
Dimensions and weight | ||
dimensions | 450 x 400 x230 mm | |
Weight | 17 kg | |
Temperature Range | ||
Storage temperature | - 20 … 70 °C | |
Working temperature | -10 … 55 °С | |
BUX 2000 | ||
Output current | Up to 2000 A | |
output power | Up to 5000 VA | |
Weight | 18 kg | |
BUX 3000 | ||
Output current | Up to 3000 A | |
output power | Up to 4800 VA | |
Weight | 15 kg | |
BUX 5000 | ||
Output current | Up to 5000 A / 7000 A | |
output power | Up to 5500 VA | |
Weight | 19 kg |
- e-Kam system with optional BUX module
- Standard Test Cable Set
- Power cable
- USB cable
- USB flash drive.
- TDMS software.
- Plastic case for BUX
- Transport case for e-Kam
- Manual
- Warranty card "GK Energoscan"
- Certificate of initial verification
Optional e-KAM equipment
- Grounding Device Test Kit
- Flashing Light
- External test enable button
- Cart
- PADS software
Guarantee period 1 год