The high-voltage pulse generator GVI-32/3 ENSK is designed for preliminary search for cable damage. Maximum voltage 32 kV. Pulse strength 3000 J. Used with a microphone to accurately determine the location of cable damage.The GVI-32/3 ENSK high-voltage pulse generator is designed to search for damage to cable lines laid in the ground using the acoustic method. The GVI-32 generator supplies voltage to the cable with a sequence of short pulses of high power and all the pulse energy comes out at the point where the cable insulation is damaged, producing a loud bang. Using a universal receiver (Digiphone+, Protrac, PP-500K) you can find the exact location of the damage.
The GVI-32/3 ENSK installation can also be used for preliminary determination of cable damage using the pulse-arc method. In this case, they are used as devices for burning damage in a short-term mode, or can be used in conjunction with a reflectometer (Reis-305, Reis-405, RI-407, STELL-4500) and an IDM unit as part of the SCAN-1 electrical laboratory.
The GVI-32/3 ENSK unit is used as part of a mobile laboratory and is not a portable testing device.
Functional features:
- High output voltage up to 32 kV (0-8.0-16.0-32 kV)
- Impulse power 3000 J
- Adjustable output voltage, 0 to 100%
Storage capacity, µF | 4 x 15 |
Maximum output voltage by steps: | |
- first stage, kV | 8 |
- second stage, kV | 16 |
- third stage, kV | 32 |
Maximum discharge pulse energy at any stage, J | 2000 |
Operating modes: | |
- manual | Yes |
- automatic, with a discharge pulse repetition interval, s | 5, 6, 7, 8, 10, 12, 16, 25, 50 |
Guarantee period 1 год