iCT1 Automatic current and voltage transformer testing device - I.S.A. - Altanova group
The iCT1 is a portable device designed for testing current, voltage and combination transformers.Functional Features
- Designed for testing current, voltage and combined transformers;
- Time saving: one connection for all tests;
- Carrying out all basic tests: measuring the transformation ratio and phase angle, taking the current-voltage characteristic, measuring resistance, error and load;
- Connection of up to 5 current transformer branches;
- Possibility of measuring the current-voltage characteristics of CTs with saturation voltages up to 2 kV and up to 30 kV using the constant voltage method;
- Built-in demagnetization system;
- Function "CT Definition": the ability to determine the passport data of the CT;
- Lightweight and compact;
- Patented technology.
The main generator has 5 outputs:
• High AC voltage output;
• Low AC output;
• DC voltage output;
• Low AC voltage output;
• Low voltage output for I-V characteristics using DC method
voltage.
High AC output
• maximum voltage 2 kV (iCT1 Standard);
• maximum current 1 A.
Low AC output
The output current can be adjusted manually from the front panel of the device.
• Imax. 6 A AC;
• Vmax. 100 V AC;
• Maximum power 200 VA.
Low DC output
The output current can be adjusted manually from the front panel of the device.
• Imax. 6 A DC;
• Vmax. 30 V DC;
• Maximum power 180 W.
Low AC output
• Maximum output voltage: 180 V AC;
• Maximum output current: 3.5 A AC;
• Maximum power output:
- Power supply 230 V: 400 VA (at cosφ < 0.225);
- Power supply 110 V: 350 VA (at cosφ < 0.175).
Low voltage output for I-V characteristic using constant voltage method (for iCT1 Advance)
• Maximum output voltage: 200 V DC;
• Maximum output current: 2 A (rms), 15 A (peak).
Output frequency
• Range: 15 - 400 Hz;
• Resolution: 10 MHz;
• Accuracy: 200 V.
Other Features of the Main Generator
• Zero crossing control: parameter generation starts and stops when zero is crossed;
• Alarm message when current is exceeded;
• Thermal protection: if the power circuit, amplifier or transformer overheats, an alarm message is displayed to the operator.
Parameter | Permission | Typical | Guaranteed |
Alternating current | |||
- 10 A | 1 mA | ±0.025%measurement ±0.025%range | ±0.05%measurement ±0.1%range |
D.C | |||
- 15 A | 1 mA | ±0.025%measurement ±0.025%range | ±0.05%measurement ±0.05%range |
Primary Side AC Voltage | |||
- 300 V | 15 mV | ±0.02%measurement ±0.02%range | ±0.05%measurement ±0.05%range |
Secondary Side AC Voltage | |||
- 2 100 V | 100 mV | ±0.02%measurement ±0.02%range | ±0.05%measurement ±0.05%range |
Constant pressure | |||
- 200 V | 10 mV | ±0.025%measurement ±0.025%range | ±0.05%measurement ±0.05%range |
Power consumption | Less than 1 kW |
dimensions | 410(H) x 340(W) x 205(D) mm |
Weight | 16 kg |
- iCT1 device
- Test cable kit
- Power cable
- Ground cable
- Ethernet cables
- USB flash drive
- Manual
- Warranty card of Energoscan Group of Companies
- Certificate of initial verification
Additional equipment:
- HVB 4000 – voltage module up to 4 kV
- Transport case
- Test cable set 18 m
- iCT1 software license
Guarantee period 1 год