as@emakgroup.ae

Working hours of the company:

MON - FRI: from 9:00 to 18:00

Order a call
Close
  1. Home
  2. Monitoring systems
  3. Switchgear monitoring system
  4. IRM READER – IntelliSAW Medium Voltage Monitoring System Data Acquisition Module
Article number: ENRGSKN-304

IRM READER – IntelliSAW Medium Voltage Monitoring System Data Acquisition Module - IntelliSAW

The IRM Reader module is designed to receive information from sensors and radio interfaces for transferring them to the CAM-5 module as part of the IntelliSAW medium equipment monitoring system. Connects from 1 to 9 to CAM-5 or integrates into an existing SCADA.

The IRM Reader is a remote monitoring unit that provides temperature, partial discharge, humidity and ambient temperature measurements. It connects to CAM-5 modules. Up to 9 IRM Reader modules can be connected to one CAM-5. Such systems are needed to monitor the condition of critical power supply assets such as switchgear, medium voltage circuit breakers and busbar trunking.

Connectivity to IRM READER:

• 12 Wireless passive temperature sensors (SAW)

• 4 air partial discharge interfaces

• 8 humidity and ambient temperature sensors

Application:

Medium distribution devices

and low voltage

Busbars

Insulated busbars

Ring main blocks

Transformers

Generator circuit breakers

on-load tap-changer

Rectifiers

Capacitor blocks

Areas of use

Generation:

  • hydroelectric power station
  • CHP
  • Power plants
  • on renewable energy sources

Industry:

  • Heavy industry
  • Metallurgical and aluminum plants
  • Production
  • Petrochemistry
  • Data Centers

Transmission and distribution

  • Step-up substations
  • Step-down substations
  • Collector substations

Equipment installation examples

A medium voltage switchgear cabinet is an example of an installation where the IRM Reader is installed in the low voltage compartment while all other sensors are installed in the high voltage compartments.

Temperature

Operating frequencies

425 – 442 MHz

Number of Temperature Sensors (SAW)

from 1 to 12

Redundancy module

up to 4 redundant antennas

RF transmit power

Pulse, -6 to 10 dBm

RF Receiver Sensitivity

-86 dBm

Stable HF reception frequency

±700 Hz

RF Polling Distance

up to 1.75 m to Mast and 2.5 m to TPD Air Interface

HF polling time

? 160 ms

Partial discharges

Number of channels

up to 4 CAM Air Interface (TPD)

Method of measurement

Ultra High Frequency (UHF)

Selectable ranges (center frequency)

300 MHz, 600 MHz and 1200 MHz

Measurement type

Noise level, surface discharge (corona), internal discharge (PD)

Measurement scale

dB, calibrated against reference source

Measurement sensitivity

100 pC at peak discharge value, at 24 kV

Polling time

100 ms

Humidity

Number of channels

up to 8 sensors connected via bus

Measurement type

Relative humidity, ambient temperature

Communication interface

Data bus

RS485 (half duplex)

Bus baud rate

4800, 9600, 19200, 38400, 57600 or 115200

Data transfer protocol

Modbus-RTU

Response time

500 ms or more (usually

Setting interface

USB

Configuration protocol

IntelliSAW Native

Dimensions and weight

Operational power (3.5 W)

48 V DC normal (24 and 60 V DC)

Dimensions (HxLxW)

81 x 142.5 x 46 mm

Weight

0.3 kg

Degree of protection

IP20

Installation method

on DIN - rail

terms of Use

from -25? up to +70?

10 – 95% relative humidity non-condensing

Maximum altitude 5000 m

The equipment is agreed upon with a technical specialist

Guarantee period 1 год