Article number: ENRGSKN-331

Combined electrical engineering laboratory SCAN-3ME - GC "Energoscan"

A set of equipment for the electrical engineering laboratory SCAN-3ME for high-voltage testing, determining the location of faults in cable lines with voltages of 0.4-35 kV, as well as testing transformer equipment

The SCAN-3ME electrical laboratory equipment set is designed for high-voltage testing, determining the location of faults in cable lines with voltages of 0.4-35 kV, as well as testing transformer equipment. The kit is mounted on any type of vehicle from GAZ-27057 to KAMAZ.

Capabilities of the electrical laboratory SCAN-3ME:

1.

Testing of power cable lines and substation equipment with alternating voltage of industrial frequency 50 Hz up to 100 kV, rectified voltage up to 70 kV.

2.

Insulation resistance measurement, voltage up to 2.5 kV;

3.

Preliminary location of cable damage using the following methods:

  • TDR reflectometry method;
  • Arc pulse method (ARC);
  • Current-coupled oscillatory discharge (ICE) method;
  • Voltage-coupled oscillatory discharge method (Decay);
  • Burning/afterburning of insulation;

4.

Accurate location of cable line damage

  • Acoustic method;
  • Induction;
  • Potential

5.

Determination of the cable line route;

6.

Determining the depth of the cable line;

7.

Selecting a cable from a bundle;

8.

Determining the location of cable sheath damage.

9.

Measuring transformer parameters:

  • Measurement of capacitance and dielectric loss tangent;
  • Transformation coefficient;
  • Direct current winding resistance;
  • Idling losses;
  • Short circuit losses;
  • Short circuit resistance

Laboratory equipment is conventionally divided into main (mounted) and additional (non-mounted) equipment. The laboratory has a modular structure; instruments, if necessary, operate independently of each other.

Set production time : 30 days

The laboratory can be additionally equipped with:

  • High-voltage VLF installation VIU SNC-36 (or equivalent);
  • Locator kit CST-15 (or equivalent);
  • Search kit CSL-10 (or equivalent);
  • Instruments for cable diagnostics;
  • Insulation parameter meter Tangent-2000 (or equivalent)
  • Transformer parameters meter Coefficient-1.3 (or analogue)
  • Microohmmeter PTF-1 (or equivalent)
  • Instruments for diagnostics of transformers.

Advantages of working with our electrical laboratories:

1.

Affordable prices

  1. ETL set (without chassis) from 5 million rubles;

2.

Equipment reliability

  1. Warranty 24 months;
  2. Extension of warranty after maintenance;
  3. Own production site;

3.

Ease of use

  1. Simple and intuitive ETL control - all units have their own control panel;
  2. All devices operate autonomously (independent of each other and the control controller);
  3. Modular design (19 inches) - easy replacement or repair of units.

4.

Technical support and service

  1. Training of Customer specialists to work with ETL;
  2. Technical consultations from the Customer’s specialists;
  3. Service and repair of ETL in the shortest possible time, replacement equipment.

5.

experience

  1. Our company has been on the market for more than 10 years;
  2. We are engaged in testing electrical equipment up to 500 kV;
  3. We use domestic and foreign developments.

Counter table

The supporting structure is used to accommodate modules and blocks. It is also the operator's workplace.

Stand type: Eurodesk. The rack is made in a 19-inch design with the ability to install equipment designed for installation in a 19-inch format. Additionally, the Eurodesk stand functions as a desktop.

Blocks management and safety

Control block;

Network block;

SCAN-3 low-voltage connection block;

Connection block with discharge and grounding device;

System operative power supply device;

Circuit breaker block;

Ground control unit;

Isolation transformer;

Semi-automatic switching system (1F);

Security and alarm system.

High voltage testing unit

VIU-100/70

Rated supply voltage - 220V;

Maximum voltage (50 Hz) - 100 kV;

Maximum rectified voltage – 70 kV;

Output power – up to 12 kVA (long-term)/20 kVA (short);

The insulation type of the high-voltage transformer is SF6 gas;

Measurement error - 3%;

High voltage pulse generator

GVI - 32 / 3,000

Rated supply voltage - 220V

Maximum power consumption – 3.5 kVA

Maximum voltage – 32 kV

Number of stages – 3 (8,16,32 kV)

Maximum stored energy - 3000 J

Pulse repetition periods – 3 and 6 seconds, single

Communication blocks

BLOCK ID-40 (Pulse-arc method ARC)

BLOCK DN-80 (Voltage oscillatory discharge method DECAY)

BLOCK DT-50 (ICM oscillatory current discharge method)

Burning installation

PU-90

Power - 220(+-10%)/ 45-60Hz

Maximum power consumption – 5.75 kVA

Maximum voltage - 15 kV DC / 30 kV with DL30

Maximum current – 90A

Number of steps – 8 pcs.

Steps:

AC, 60V/92A step (110A max)

alternating current, stage 230 V / 23 A

AC, stage 500 V / 11 A

AC, stage 1500 V / 3.5 A

alternating current, stage 2 600 V / 2 A

DC, stage 5,000 V / 1 A

DC, stage 8,500 V / 0.65 A

DC, stage 15,000 V / 0.35 A

Reflectometer

FLIGHT-305

Distance ranges – from 0 to 51 km

Pulse voltage – from 7V to 25V

Sampling frequency - 200 MHz

Internal memory – 500 reflectograms;

Supported methods:

  • Reflectometry (TDR);
  • Arc Pulse (ARC);
  • Oscillatory current discharge (ICM);
  • Oscillatory voltage discharge (DECAY).

Induction search kit

PC -2500

Stationary generator:

  • Frequencies: 1024/2048 (Hz)
  • Output power – 2500 W
  • Maximum output current – 50 A

Portable generator:

  • Frequencies: 273/2187.5/6562.5/26250 (Hz)
  • Output power – 10 W

Receiver:

  • Frequencies: 273/1024/2048/6562.5 /26250Hz
  • Maximum detectable route depth: 6m
  • Depth accuracy: ±5%+10 cm
  • Finding accuracy:10cm
  • Battery operating time: at least 20 hours
  • Receiver weight: 0.65 kg

Included:

  • Acoustic sensor;
  • Contact pins;
  • Pliers for identifying “your” cable.

Dielectric loss measurement unit

(without bridge)

The IDP unit provides measurement of the capacitance and dielectric loss tangent of test objects at an alternating current voltage with a frequency of 50 Hz up to 10 kV within the limits provided by the Tangent-2000 meter.

The IDP block includes:

  • Place for AC bridge type Tangent2000;
  • High-voltage switch “DIRECT-INVERSION”.

Switching occurs in a high-voltage switch “DIRECT-INVERT”. The switch allows, after starting the test in the IDP mode, to switch the measurement circuit without re-switching the high-voltage conductors.

Low voltage connection block

The low-voltage connection block is divided into 4 sections (“GZCH control panel”, “Reflectometer connection panel”, “External equipment connection panel”, “Low-voltage measurement panel”) and performs the following functions:

  1. Audio frequency generator control;
  2. Connecting external equipment up to 2.5 kV to the test object;
  3. Connecting the reflectometer to the test object;
  4. Connecting measuring instruments to the test object (power transformer) in three-phase mode (400V/10A).

Rack for connections to BNI

The laboratory is equipped with a free-standing rack for connecting cables to the BNI unit in the high-voltage compartment.

The rack contains connectors for connecting low-voltage test cables and external power supply to a three-phase autotransformer. All low-voltage test cables are protected by 10A fuse links against exceeding the maximum current and voltage of 400V. Fuse links are grouped near the corresponding connectors.

Cable drum and cable system

The system is made in the form of cable drums on a steel frame with a braking device. The system includes the following cable reels:

  • Drum with high-voltage shielded cable for testing with rectified voltage up to 70 kV – 30 m;
  • Drum with network cable – 30m;
  • Drum with working grounding cable 10mm2 –30m;
  • Drum with protective grounding cable 16mm2 (with current collection clips) – 30m;
  • Drum with wire for testing with alternating voltage of industrial frequency - 30 m (installed on a dielectric stand, with the ability to test without completely unwinding the wire);
  • Coil with control grounding wire – 25m;
  • Drum with a flexible cable for supplying three-phase power to the low-voltage measurement unit - 30 m;
  • Drum for “VP Cable” for IDP Block – 1 pc.;
  • Drum for “Cable Cx” for IDP Block – 1 pc.;
  • Drum for “Cable E” for IDP Block - 1 pc.;
  • Drum with flexible 4-core cable for low-voltage measurements with alligator clips - 2x30m;

Optional equipment

  • First aid kit for automobiles
  • Dielectric boots - 2 pcs.
  • Orange protective helmet - 2 pcs.
  • Dielectric mat? - 2 pcs.
  • Set of warning posters - 1 set.
  • Dielectric gloves – 2 pcs.
  • High-voltage insulating stands - 5 pcs.
  • Low voltage indicator – 1 pc.
  • Operating rod up to 15 kV – 1 pc.
  • Operating rod up to 110 kV – 1 pc.
  • Vehicle grounding pin – 1 pc.
  • Megaohmmeter E6-32 – 1 pc.
  • Curvimeter (road wheel) – 1 pc.

Documentation set

  • Laboratory Operation Manual
  • Form
  • Album of electrical circuits
  • Periodic testing program and methodology? laboratories
  • Acceptance test protocol?
Warranty
  • Guaranteed? period for equipment - 12 months. Is the vehicle warranty established in accordance with the service warranty? a book? manufacturer's plant.

List of equipment for the ETL SCAN-3ME kit:

  • Eurodesk type counter desk;
  • Control block;
  • Network block;
  • SCAN-1 low-voltage connection block;
  • Connection block with discharge and grounding device;
  • System operative power supply device;
  • Circuit breaker block;
  • Ground control unit;
  • Isolation transformer;
  • Semi-automatic switching system (1F);
  • High voltage installation 100/70 kV 20 kVA (short term);
  • Burning (15kV/90A/8 stages?);
  • High-voltage pulse generator (8/16/32 kV, 2000 J);
  • Coordinating devices (ARC, ICM, DECAY);
  • PC-2500 search kit;
  • Reis-305 reflectometer;
  • E6-32 megohmmeter;
  • Dielectric loss measurement unit (without bridge);
  • Control and safety system 1 phase version;.
  • Cable reel system and cables? 30m;
  • Operation manual + diagrams + Passport;
  • Warranty card "Energoscan" 12 months;

Guarantee period 12 месяцев

Leave a request

Leave a request and our manager will contact you within an hour
callback
1
$settings->wid3get_name}
Emak Group

What can we offer you