MFT1815 Megger Multifunction Tester - Megger
Designed for measuring and testing all parameters of low-voltage networks and electrical installations (wiring, RCD, grounding, etc.) with voltage up to 1 kV. Certificate of initial verification -1600 rublesElectrical safety parameter meter MFT 1815 , manufactured by M egger (England), is designed for measuring and testing parameters of electrical installations (wiring, RCD, grounding, etc.) with voltages up to 1000 V.
MFT 1815 allows you to test insulation voltages of 250V and 500V with resistance measurements in the range from 10kOhm to 500MOhm. The integrity of the circuit is determined at a current of 200 mA.
Also, the multifunctional tester MFT 1815 carries out testing of RCDs with a nominal value of 30 mA, 100 mA, 300 mA, 500 mA. Testing is carried out with current: 1xI in position 0? and 180.
Measuring parameters of the MFT 1815 M egger loop conducts two-wire method. 2-wire testing of electrical circuits is performed using only two test leads, measurements - Phase - Ground / Phase - Zero / Phase - Phase. A third wire, which could cause confusion in identifying the part of the circuit under test, is not needed. Measurements take place in the voltage range from 28V to 280V AC in single-phase circuits to 480V in three-phase circuits. Short circuit current (SC) is calculated up to 20kA using the measured voltage and loop resistance.
The multifunction tester MFT 1815 measures alternating voltage up to 600V, allows you to measure frequency in the range from 15Hz to 400Hz and determine the phase sequence.
The multifunctional tester MFT-1815 has a large LCD display with digital display and imitation of an analog scale. Selecting test or measurement mode is simple and convenient, and is also separated by color gradation. Much attention is paid to testing safety; if the electrical installation being tested is energized, the operator will be notified about this, and the device will not fail (within the CATIV standard).
The multifunctional tester MFT1815 M egger is made in a shock-resistant, moisture-dust-proof housing (IP 54).
Functional features of the MFT 1815 device:
- Measuring network voltage and frequency
- 250V and 500V insulation testing
- Measuring loop resistance and calculating short-circuit current
- Testing of RCDs rated 30 mA, 100 mA, 300 mA, 500 mA.
- RCD current testing: 1xI in position 0? and 180
MFT1815 Megger Specifications :
Insulation testing | |
Insulation Test Voltage | 500 V, 250 V |
Short circuit/load current | 1.5 mA/1 mA |
Resistance measurement and conductivity test | |
Resistance measurement ranges | 0.01 Ohm – 99.9 Ohm; 100 Ohm – 99.9 kOhm |
Max. Voltage | 5V±1V |
Current | 205 mA ± 5 mA |
Loop testing | |
Testing | Phase-Phase, Phase-Neutral(Zero), Phase-Ground |
Phase-Ground Voltage | 48 V – 280 V (45 Hz-65 Hz) |
Voltage Phase-Phase | 48 V – 500 V (45 Hz-65 Hz) |
Loop resistance measurement range | 0.01 Ohm – 999 Ohm |
Short circuit current | Up to 20 kA |
RCD test | |
RCD type | A, AC |
Currents | 30 mA, 100 mA, 300 mA, 500 mA |
Mode | Rated current testing |
Measuring Network Parameters | |
Measuring network voltage and frequency | 10V – 600V (15Hz-400Hz) |
Common parameters | |
Operating temperature range | -10 °С…+55 °С |
Work from: | 6 AA batteries |
Weight | 1 kg (with batteries) |
dimensions | 150 mm x 85 mm x 235 mm |
Protection from dust and moisture | IP 54 |
Safety | CAT IV |
Basic equipment MFT 1815 :
- Multi-function tester MFT1815 Megger
- Manual
- CD with instruction manual
- SP5 probe with test start button
- Neck strap
- 3 test cables with probes and crocodile clips
- Test cables with Euro plug
- Plastic case
- Warranty card of GC "Energoscan"
Additional equipment:
- Soft transport bag
- Test cables with 10 A fuses with alligator clips and probes
- ETL30, 30 m extension cable
- ETL50, 50 m extension cable
- Power supply from 12 V
Guarantee period 3 года