MFT1835 Megger multi-function tester - Megger
Designed for measuring and testing all parameters of low-voltage networks and electrical installations (wiring, RCD, grounding, etc.) with voltage up to 1 kV.Meter of electrical safety parameters of installations MFT 1835 , manufactured by Megger (England), is designed for measuring and testing parameters of electrical installations (wiring, RCD, grounding, etc.) with voltages up to 1000 V.
The MFT 1835 allows you to test insulation voltages of 100V, 250V, 500V and 1000V with resistance measurements ranging from 10kΩ to 999MΩ. The integrity of the circuit is determined at a current of 200mA and 15mA.
The MFT1835 meter also tests RCDs with ratings of 10mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000 mA. Testing is carried out with current: ½ x I, 1 x I, 2 x I and 5 x I in position 0? and 180.
The MFT 1835 loop parameters are measured two-wire method. 2-wire testing of electrical circuits is performed using only two test leads, measurements - Phase - Ground / Phase - Zero / Phase - Phase. A third wire, which could cause confusion in identifying the part of the circuit under test, is not needed. Measurements take place in the voltage range from 28V to 280V AC in single-phase circuits and up to 480 in three-phase circuits. Short circuit current (SC) is calculated up to 20kA using the measured voltage and loop resistance.
The MFT 1835 device measures alternating voltage up to 600V, allows you to measure frequency in the range from 15Hz to 400Hz and determine the phase sequence.
The resistance of grounding devices is measured using a 2- and 3-wire circuit using the pin method. Currents 0.45 mA or 4.5 mA, resistance resolution 0.01 ohm, noise rejection 20 V peak-to-peak.
The MFT1835 meter has a large LCD display with digital display and imitation of an analog scale. Selecting test or measurement mode is simple and convenient, and is also separated by color gradation. Much attention is paid to testing safety; if the electrical installation being tested is energized, the operator will be notified about this, and the device will not fail (within the CATIV standard).
The MFT1835 device has an internal memory and can save all test data and also transfer it to a PC via Bluetooth.
MFT 1835 M egger is made in a shock-resistant, moisture-dust-proof housing (IP 54).
Functional features of the MFT 1835 device:
- Measuring network voltage and frequency
- Insulation testing with voltage 250V, 500V,1000V
- Measuring loop resistance and calculating short-circuit current
- Testing of RCDs rated 10mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000 mA
- RCD current testing: ½ x I, 1 x I, 2 x I and 5 x I in position 0? and 180
- Checking grounding devices using a 2- and 3-wire scheme and the pinless method
- Inner memory
- Transfer data to PC
Differences from MFT 1825:
- Insulation testing with voltage 100V,250V, 500V,1000V
- Inner memory
- Transfer data to PC
MFT1835 Specifications :
Insulation testing | |
Insulation Test Voltage | 1000 V, 500 V, 250 V, 100 D |
Short circuit/load current | 1.5 mA/1 mA |
Resistance measurement and conductivity test | |
Resistance measurement ranges | 0.01 Ohm – 99.9 Ohm; 100 Ohm – 99.9 kOhm |
Max. Voltage | 5V±1V |
Current (user selectable) | 205 mA ± 5 mA; 15 mA ± 5 mA |
Loop testing | |
Testing | Phase-Phase, Phase-Neutral(Zero), Phase-Ground |
Phase-Ground Voltage | 48 V – 280 V (45 Hz-65 Hz) |
Voltage Phase-Phase | 48 V – 500 V (45 Hz-65 Hz) |
Loop resistance measurement range | 0.01 Ohm – 999 Ohm |
Short circuit current | Up to 20 kA |
RCD test | |
RCD type | A, AC, S; B, three-phase RCDs (without ground) |
Currents | 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000 mA |
Mode | 1/2I, I, 2I, 5I; automatic test |
Ground resistance measurement | |
Mode | 2-pole, 3-pole, ART, contactless |
Measuring Network Parameters | |
Measuring network voltage and frequency | 10V – 600V (15Hz-400Hz) |
True RMS (true value measurement) | There is |
Determining the phase order | There is |
Common parameters | |
Operating temperature range | -10 °С…+55 °С |
Work from: | 6 pcs 1.2V NiMH rechargeable batteries |
Interface, memory | Bluetooth; 1000 results |
Weight | 1 kg (with batteries) |
dimensions | 150 mm x 85 mm x 235 mm |
Protection from dust and moisture | IP 54 |
Safety | CAT IV |
Basic equipment MFT 1835 Megger :
- Tester MFT1835
- Manual
- CD with instruction manual
- SP5 probe with test start button
- Neck strap
- 3 test cables with probes and crocodile clips
- Test cables with Euro plug
- Plastic case
- Warranty card of GC "Energoscan"
- Certificate of initial verification
Additional equipment MFT1835:
- Soft transport bag
- Test cables with 10 A fuses with alligator clips and probes
- ETL30, 30 m extension cable
- ETL50, 50 m extension cable
- Power supply from 12 V
- Set for measuring ground resistance using rods.
Guarantee period 3 года