Insulation Tester, Fluke 1555 - Fluke
Insulation resistance meter Learn trends, eliminate doubts The 1555 Insulation Tester is designed for digital insulation testing up to 10kV, making it ideal for testing a wide range of high voltage equipment including high voltage switchboards, motors, generators and cables. Fluke insulation testers can now be used across the entire IEEE 43-2000 test voltage range, come with a best-in-class 3-year warranty, and are CAT IV 600 V rated. Measurement memory and PC connectivity make The 1555 tester is the ideal tool for predictive or predictive maintenance programs designed to detect potential equipment failures before they occur....Insulation resistance meter
Learn trends, eliminate doubts
The 1555 Insulation Tester is designed for digital insulation testing up to 10kV, making it ideal for testing a wide range of high voltage equipment including high voltage switchboards, motors, generators and cables.
Fluke insulation testers can now be used across the entire IEEE 43-2000 test voltage range, come with a best-in-class 3-year warranty, and are CAT IV 600 V rated. Measurement memory and PC connectivity make The 1555 tester is the ideal tool for predictive or predictive maintenance programs designed to detect potential equipment failures before they occur.
Electrical characteristics
The error of the tester is normalized within one year after calibration in the operating temperature range from 0 °C to 35 °C. For operating temperatures outside the specified range (-20°C to 0°C and 35°C to 50°C), add ±0.25% per °C, within 20% of range add ±1% per °C
Test voltage | Range | Accuracy (± readings) |
250 V | < 200 kOhm from 200 kΩ to 5 GΩ 5 GΩ to 50 GΩ > 50 Gom | not standardized 5 % 20 % not standardized |
500 V | < 200 kOhm from 200 kΩ to 10 GΩ from 10 GΩ to 100 GΩ > 100 GΩ | not standardized 5 % 20 % not standardized |
1000 V | < 200 kOhm from 200 kΩ to 20 GΩ from 20 GΩ to 200 GΩ > 200 GΩ | not standardized 5 % 20 % not standardized |
2500 V | < 200 kOhm from 200 kΩ to 50 GΩ from 50 GΩ to 500 GΩ > 500 GΩ | not standardized 5 % 20 % not standardized |
5000 V | < 200 kOhm from 200 kΩ to 100 GΩ from 100 GΩ to 1 TΩ > 1 TOM | not standardized 5 % 20 % not standardized |
10000 V (1555 only) | < 200 kOhm from 200 kΩ to 200 GΩ from 200 GΩ to 2 TΩ > 2 TOM | not standardized 5 % 20 % not standardized |
Histogram range | from 0 to 1 TOM |
Test voltage error | -0%, +10% at 1mA load current |
Suppression of induced current from the network | Maximum 2mA |
Charge rate for capacitive load | 5 seconds per uF |
Discharge rate for capacitive load | 1.5 s/uF |
Range | Error | |
Leakage current measurement | 1 nA to 2 mA | ±(5% + 2nA) |
Capacitance measurement | 0.01 uF to 15.00 uF | ± (15% of reading + 0.03 uF) |
Timer | Range 0 to 99 minutes | Permission Setpoint: 1 minute Indication: 1 second |
Live Circuit Warning | Warning range 30 V to 660 V AC/DC, 50/60 Hz | Voltage error ±(15% + 2V) |
General characteristics | |||
Display |
| ||
Nutrition |
| ||
Charger Input (Variable) |
| ||
This Class II (double insulated) appliance is supplied with a Class 1 (grounded) power cord. The protective earth pin is not connected internally. The additional output is only used to connect the plug. | |||
Dimensions |
| ||
Weight |
| ||
Temperature (working) |
| ||
Temperature (storage) |
| ||
Humidity |
| ||
Height |
| ||
Case protection degree |
| ||
Input overload protection |
| ||
Electromagnetic compatibility |
| ||
Certification | |||
Security category |
| ||
Degree of pollution |
|
Product code 58749135
brand Fluke
State Новое
Manufacturer country США