Fluke 435 II Energy and Power Quality Analyzer - Fluke
Energy and power quality analyzer Advanced Power Quality Functions, Unprecedented Power Quality Analysis Capabilities The Fluke 435 II Power Quality Analyzer should be treated as insurance. Whatever happens in your plant, with the 435 II you will always be prepared for any situation. Equipped with advanced power quality evaluation and loss value monetary functions, this model can solve any electrical problem. Areas of use Data Acquisition with PowerWave Technology - Quick RMS measurements to quickly view each waveform so you can see how voltage, current, and frequency interact. Inverter Efficiency - Power Inverter Efficiency...Energy and power quality analyzer
Advanced Power Quality Functions, Unprecedented Power Quality Analysis Capabilities
The Fluke 435 II Power Quality Analyzer should be treated as insurance. Whatever happens in your plant, with the 435 II you will always be prepared for any situation. Equipped with advanced power quality evaluation and loss value monetary functions, this model can solve any electrical problem.
Areas of use
- Data Acquisition with PowerWave Technology - Quick RMS measurements to quickly view each waveform so you can see how voltage, current, and frequency interact.
- Inverter Efficiency - Power Inverter Efficiency
- Electricity monetization - calculation of energy losses due to its poor quality in monetary terms
- Energy assessment - calculation of improvements before and after installation in energy consumption to adjust energy-saving devices
- Basic Troubleshooting - Quick On-Screen Diagnostics to Restore Network Operation
- Prevention - Detect and prevent power quality problems before they lead to downtime
- Long-term analysis - identifying difficult-to-find and intermittent problems
- Load Study - Verify Electrical System Capabilities Before Adding Loads
Product Features | ||||
Model | Measuring range | Permission | Accuracy | |
Volt | ||||
RMS (V.A.+D.) | 435-II | 1...1000 V - between phase and neutral | 0.01 V | ± 0.1% of rated voltage**** |
Peak voltage | 1...1400 V peak voltage | 1 V | 5% of rated voltage | |
Voltage form factor (CF) | 1.0 > 2.8 | 0.01 | ± 5% | |
W(rms)? | 435-II | 0.1 V | ± 0.2% of rated voltage | |
Vfund (fundamental) | 435-II | 0.1 V | ± 0.1% of rated voltage | |
Current strength (accuracy without clamp error) | ||||
Amps (AC+DC) | i430-Flex 1x | from 5 to 6000 A | 1 A | ± 0.5% ± 5 units ml. res. |
i430-Flex 10x | 0.5...600 A | 0.1 A | ± 0.5% ± 5 units ml. res. | |
1 mV/A 1x | from 5 to 2000 A | 1 A | ± 0.5% ± 5 units ml. res. | |
1 mV/A 10x | 0.5...200 A (only AC) | 0.1 A | ± 0.5% ± 5 units ml. res. | |
A (peak value) | i430-Flex | 8400 A (peak current) | 1 A (rms) | ± 5% |
1 mV/A | 5500 A (peak value) | 1 A (rms) | ± 5% | |
Current Form Factor (CF) | 1...10 | 0.01 | ± 5% | |
A(av.sq.)? | i430-Flex 1x | from 5 to 6000 A | 1 A | ± 1% ± 10 units ml. res. |
i430-Flex 10x | 0.5...600 A | 0.1 A | ± 1% ± 10 units ml. res. | |
1 mV/A 1x | from 5 to 2000 A | 1 A | ± 1% ± 10 units ml. res. | |
1 mV/A 10x | 0.5...200 A (only AC) | 0.1 A | ± 1% ± 10 units ml. res. | |
Afund (fundamental frequency current) | i430-Flex 1x | from 5 to 6000 A | 1 A | ± 0.5% ± 5 units ml. res. |
i430-Flex 10x | 0.5...600 A | 0.1 A | ± 0.5% ± 5 units ml. res. | |
1 mV/A 1x | from 5 to 2000 A | 1 A | ± 0.5% ± 5 units ml. res. | |
1 mV/A 10x | 0.5...200 A (only AC) | 0.1 A | ± 0.5% ± 5 units ml. res. | |
Hz | ||||
Hz | Fluke 435 at 50 Hz nominal | 42.500–57.500 Hz | 0.001 Hz | ±0.01Hz |
Fluke 435 at 60 Hz nominal | 51.000 to 69.000 Hz | 0.001 Hz | ±0.01Hz | |
Power | ||||
Watts (VA, VAr) | i430-Flex | Max. 6000 MW | 0.1 W...1 MW | ± 1% ± 10 units ml. res. |
1 mV/A | Max. 2000 MW | 0.1 W...1 MW | ± 1% ± 10 units ml. res. | |
Power factor (Cosj/DPF) | 0...1 | 0.001 | ± 0.1% at rated load conditions | |
Energy | ||||
kWh (kVAh, kvarh) | i430-Flex 10x | Depends on clamp rating and voltage | ± 1% ± 10 units ml. res. | |
Energy loss | i430-Flex 10x | Depends on clamp rating and voltage | ± 1% ± 10 units ml. res., excluding resistance accuracy | |
Harmonics | ||||
Order of the harmonic component (n) | DC, grouping 1 to 50: Harmonic groups according to IEC 61000-4-7 | |||
Interharmonic order (n) | OFF, grouping 1 to 50: Harmonics and interharmonics subgroups according to IEC 61000-4-7 | |||
Volts | %f | 0.0-100% | 0.1% | ± 0.1% ± nx 0.1% |
%r | 0.0-100% | 0.1% | ± 0.1% ± nx 0.4% | |
Absolute value | 0.0...1000 V | 0.1 V | ± 5% * | |
THD (Total Harmonic Distortion) | 0.0-100% | 0.1% | ± 2.5% | |
Amps | %f | 0.0-100% | 0.1% | ± 0.1% ± nx 0.1% |
%r | 0.0-100% | 0.1% | ± 0.1% ± nx 0.4% | |
Absolute value | 0.0...600 A | 0.1 A | ± 5% ± 5 units ml. res. | |
THD (Total Harmonic Distortion) | 0.0-100% | 0.1% | ± 2.5% | |
watts | %f or %r | 0.0-100% | 0.1% | ± nx 2% |
Absolute value | Depends on clamp rating and voltage | — | ± 5% ± nx 2% ± 10 units ml. res. | |
THD (Total Harmonic Distortion) | 0.0-100% | 0.1% | ± 5% | |
Phase shift | -360 to +0° | 1° | ±nx 1° | |
Flicker | ||||
Plt, Pst, Pst (1 min.) Pinst | 0.00...20.00 | 0.01 | ± 5% | |
Imbalance | ||||
Volts | % | 0.0 - 20.0% | 0.1% | ± 0.1% |
Amps | % | 0.0 - 20.0% | 0.1% | ± 1% |
Network control signals | ||||
Threshold levels | Thresholds, limits and signal duration programmable for two signal frequencies | — | — | |
signal frequency | 60...3000 Hz | 0.1 Hz | ||
Relative stress (%) | 0.0-100% | 0.10% | ±0.4% | |
Absolute voltage averaged over 3 s (V 3s) | 0.0 to 1000 V | 0.1 V | ± 5% of rated voltage |
General characteristics | |
Frame | Rugged shockproof housing with built-in protective case IP51 splash and dust resistant according to IEC60529 when used on a tilt stand. Shock and vibration protection. Shock 30 g, vibration: sine wave 3 g, random 0.03 g 2 /Hz per MIL-PRF-28800F class 2. |
Display | Brightness: 200 cd/m2 typically using AC adapter, 90 cd/m2 typically using battery power. Size: 127 * 88mm (153mm / 6.0 inches diagonal). LCD resolution: 320*240 pixels. Contrast and Brightness Adjustment: User adjustable, temperature compensated. |
Memory | SD card 8 GB (SDHC compliant, FAT32 formatted), up to 32 GB optional. Screen protection and multiple memory modules for storing data, including recordings (depending on the size of the memory). |
Real time clock | Date and time stamp in Trend mode, Transient display, System Monitor, and event logging |
terms of Use | |
Operating temperature range | from 0 to +40 °C; +40 to +50 °C without battery |
Storage temperature | -20 to +60 °C |
Humidity | +10 °C ~ +30 °C: 95% RH non-condensing +30 °C ~ +40 °C: 75% RH non-condensing +40 °C ~ +50 °C: 45% RH non-condensing |
Maximum Altitude | Up to 2000 m (6666 ft) for CAT IV 600 V, CAT III 1000 V. Up to 3000 m (10,000 ft) for CAT III 600 V, CAT II 1000 V. Maximum storage altitude 12 km (40,000 ft) |
Electromagnetic compatibility (EMC) | Conforms to GOST R 51522.1-2011 (IEC 61326-1:2005) for radiation and immunity to radio interference |
Interfaces | mini USB-B, isolated USB port for PC, SD card slot behind tool battery |
Guarantee | Three years (parts and labor) for main unit, one year for accessories |
* ± 5% if ? 1% of rated voltage; ± 0.05% of rated voltage if < 1% of rated voltage.
** Rated frequency 50/60 Hz according to IEC 61000-4-30
*** 400Hz measurements are not supported for flicker, network signals, and monitor mode.
****for rated voltage 50-500 V
Product code 58749170
brand Fluke
State Новое
Manufacturer country США