Current Loop Calibrator, Fluke 707 - Fluke
Current loop calibrator Fluke 707 Calibrator Features: Large display and user-friendly one-handed interface; Simultaneous display of mA and % for quick and easy interpretation of readings; 0.015% is the best mA accuracy among calibrators in this price range; 1µA resolution for mA measurement and simulation; Function of automatic checking of linearity of transducers with a step of 25%, started by pressing a button; "Span Check" function to quickly determine the level of the calibration signal from 0% to 100%; - Choice between slow and fast sawtooth (ramp), as well as step-by-step (in 25% steps) increase in...Current loop calibrator
Fluke 707 Calibrator Features:
- Large display and user-friendly one-handed interface;
- Simultaneous display of mA and % for quick and easy interpretation of readings;
- 0.015% is the best mA accuracy among calibrators in this price range;
- 1µA resolution for mA measurement and simulation;
- Function of automatic checking of linearity of transducers with a step of 25%, started by pressing a button;
- "Span Check" function to quickly determine the level of the calibration signal from 0% to 100%;
- Choice between slow and fast sawtooth (ramp), as well as step-by-step (in 25% steps) increase in the current strength at the output of the calibrator for the functional test of the current loop;
- Internal 24V loop power, so you can power up and read transducer parameters at the same time without using a DMM; - DC voltage measurement up to 28 V;
- One easy-to-replace 9V battery;
- Factory settings allow operation with 0 - 20 mA or 4 - 20 mA circuits.
- Progressive current output setting with 1 µA and 100 µA resolution.
The Fluke 707 is compatible with HART equipment. The HARTTM function allows the instrument to be connected in series to the current loop, provided that the load resistance between the device under test and the 24V power supply must be at least 250 ohms.
Functional characteristics | ||
Current measurement | Range Permission Accuracy | 0 ... 24 mA 0.001 mA 0.015% of reading + 2 u |
Current generation | Range Accuracy Power | 0 ... 20 mA or 4 ... 20 mA 0.015% of reading + 2 u 1200 ohms at 24 mA, 950 ohms at 20 mA in "Hart mode" |
Current simulation | Range Accuracy Requires an external power supply | 0 ... 20 mA or 4 ... 20 mA 0.025% of reading + 2 DU 12 - 30 V |
Current loop supply | During measurement mA, 24 V | |
Voltage measurement | Range Permission Accuracy | 0 ... 28 V DC voltage 1 mV 0.015% of reading + 2 u |
Environmental requirements | ||
Working temperature | -10 ºC ... 55 ºC | |
Storage temperature | -30 ºC ... 60 ºC | |
Humidity (non-condensing) | 0 … 90% (0 ?C ... 35 ?C); 0 ... 70% (35°C ... 55°C) | |
Temperature coefficient | -10 ?C ... 18 ?C, 28 ?C ... 55 ?C, ±0.005% of range per ?C | |
Safety | ||
Electrical safety standard | CSA C22.2 No. 1010.1:1992 | |
EMC | EN50082-1:1992 and EN55022:1994 Class B | |
Max Voltage | 30 V | |
Mechanical and general characteristics | ||
Size | 152 x 70 x 41mm | |
Weight | 340 g | |
Battery type | One 9 V battery type "Krona" |