Particle counter, Fluke 985 - Fluke

Particle counter The new Fluke 985 Particle Counter is the first choice for heating, ventilation and air conditioning (HVAC) professionals. From filter testing to basic indoor air quality research, the Fluke 985 Particle Counter provides a portable solution for airborne particle concentration measurement. The Fluke 985 can be used to respond immediately to occupant complaints or as part of a comprehensive preventive maintenance program. With the Fluke 985 you can: Measure filter efficiency Observe industrial premises with a particularly clean atmosphere Anticipate indoor air quality levels and work confidentially with experts on...

Particle counter

The new Fluke 985 Particle Counter is the first choice for heating, ventilation and air conditioning (HVAC) professionals. From filter testing to basic indoor air quality research, the Fluke 985 Particle Counter provides a portable solution for airborne particle concentration measurement. The Fluke 985 can be used to respond immediately to occupant complaints or as part of a comprehensive preventive maintenance program.

With the Fluke 985 you can:

  • Measure filter efficiency
  • Observe industrial premises with a particularly clean atmosphere
  • Anticipate indoor air quality levels and work confidentially with experts on the subject.
  • Determine particle sources for remediation
  • Report to clients on the effectiveness of restoration work
  • Conduct additional work to demonstrate the need for maintenance and restoration work

With a large screen, intuitive interface icons and on-screen data presentation, the Fluke 985 allows users to take more measurements quickly, with less time navigating between screens to acquire data. The Fluke 985 is lightweight and easy to use with convenient export options via USB cable and flash drive - easy to view and analyze data anywhere, anytime.

Measured characteristics
Channels
0.3 µm, 0.5 µm, 1.0 µm, 2.0 µm, 5.0 µm, 10.0 µm
Flow rate
2.83 l/min (0.1 cfm)
Light source
775-795nm, 90mW, class 3B laser
Counting modes
Direct counting, #/m3, #/ft3, #/l in accumulative or differential mode
Counting factor
50% at 0.3 µm; 100% for particles > 0.45 µm (according to ISO 21501)
Zero counter
1 unit/5 minutes (JIS B9921)
Concentration limits
10% per 4,000,000 particles per sq. ft. (according to ISO 21501)
Memory
10,000 entries (round robin)
Alarms
Calculations, battery low, sensor failure
Delay time
0 to 24 hours
Sample entry
Isokinetic test
Safety
Management with administrator password (optional)
Communication mode
USB or Ethernet
Dimensions (L x W x H), cm
27.2 x 9.9 x 5.3
Weight
0.68 kg
Power supply, AC adapter
100-240 VAC 12 VDC current, 2.5 A
Battery
Li-ion 7.4V 2600mAh; 10 hours typical use
(5 hours of continuous measurements) / 3.5 hours
Calibration
PSL particles in air (according to the requirements of the National Institute of Standards and Technology (USA))
Working conditions
10 - 40 °C/< 95% r.h. humidity non-condensing
Storage conditions
-10 to 50 °C/< 98% r.h. humidity non-condensing
Guarantee
One year
Accessories included in the package
USB and Ethernet convenient charging base, ENET CAT5E cable (2 m), USB-A-MINI-B cable (2 m), 12 VDC power supply input filter, zero counter, filter adapter, sample inlet protection cap, hard case, quick start guide and user manual on CD
Particle counter ? Fluke 985 Indoor Air Quality Particle Counter
Particle counter, indoor air quality, HVAC air quality
Fluke Particle Counter for Indoor Air Quality Testing and Analysis

Product code 58749203

brand Fluke

State Новое

Manufacturer country США

Leave a request

Leave a request and our manager will contact you within an hour
callback
1
$settings->wid3get_name}
Emak Group

What can we offer you