Cable NAYY / NAYY-fl / NAYY-LS - STP
general information Cables with rated operating voltage 0.66; 1.0; 3.0 kV are used for the transmission and distribution of electrical energy at production facilities with low and high humidity, on special cable racks, in blocks of residential buildings, in the open air, in rivers and lakes located at an altitude of up to 4300 m above sea level. The use of these cables in trenches (underground) is not recommended. DESIGN Twisted current-carrying copper or aluminum single or multi-wire conductor of round or shaped shape PVC or XLPE insulation PVC sheath Production of conductive wires Type of conductive cores according...general information
Cables with rated operating voltage 0.66; 1.0; 3.0 kV are used for the transmission and distribution of electrical energy at production facilities with low and high humidity, on special cable racks, in blocks of residential buildings, in the open air, in rivers and lakes located at an altitude of up to 4300 m above sea level. The use of these cables in trenches (underground) is not recommended.
DESIGN
- Twisted current-carrying copper or aluminum single or multi-wire conductor of round or shaped shape
- PVC or XLPE insulation
- PVC sheath
Production of conductive wires
Type of conductive cores according to the number of wires forming them | Section, mm2 Round / Shaped |
single wire | 1.5 / 10 / - |
stranded | 16 / 240 / 25 / 185 |
Cable specifications
Cable brand | Conductor cross section, mm2 | Approximate cable diameter, mm | Approximate cable weight, kg/km | Maximum electrical resistance of the conductive core at 20°С, Ohm/km, no more |
NAYY / NAYY-fl / NAYY-LS 1.0 kV | 1 x 16 1 x 25 1 x 35 1x50 1x70 1x95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 | 10 eleven 12 14 16 18 19 21 24 26 thirty 33 | 119 162 199 263 336 447 533 662 807 1013 1250 1650 | 1.91 1.20 0.87 0.64 0.443 0.320 0.253 0.206 0.164 0.125 0.100 0.0778 |
Cable specifications
Cable brand | Conductor cross section, mm2 | Approximate cable diameter, mm | Approximate cable weight, kg/km | Maximum electrical resistance of the conductive core at 20°С, Ohm/km, no more |
NAYY / NAYY-fl / NAYY-LS 1.0 kV | 2x16 2x25 2x35 2x50 3x16 3x25 3x35 3x50 3x70 3x95 3 x 120 3 x 150 3 x 185 3 x 240 4x2.5 4x4.0 4x6.0 4x10 4x16 4x25 4x35 4x50 4x70 4x95 4 x 120 4 x 150 4x185 4 x 240 5x2.5 5x4.0 5 x 6.0 5 x 10 5 x 16 5 x 25 5 x 35 | 17.8 22.2 24.6 28.6 20 23 25 29 33 38 41 45 50 56 eleven 12 14 15 18 21 25 28 32 36 42 45 51 56 63 12 13 15 16 20 24 28 31 | 450 684 843 1135 485 681 870 1148 1512 1976 2324 2961 3552 4439 167 236 286 396 569 826 1029 1365 1828 2358 2812 3542 4255 5322 192 271 332 475 662 963 1206 | 1.91 1.20 0.87 0.64 1.91 1.20 0.87 0.64 0.443 0.320 0.253 0.206 0.164 0.125 12.4 7.41 5.11 3.08 1.91 1.20 0.87 0.64 0.443 0.320 0.253 0.206 0.164 0.125 12.4 7.41 5.11 1.91 1.20 0.87 |
Cable specifications
Cable brand | Conductor cross section, mm2 | Approximate cable diameter, mm | Approximate cable weight, kg/km | Maximum electrical resistance of the conductive core at 20°С, Ohm/km, no more |
NAYY / NAYY-fl / NAYY-LS 1.0 kV | 3 x 4+1 x 2.5 3 x 6+1 x 4.0 3 x 10+1 x 6.0 3 x 16+1 x 10 3 x 25+1 x 16 3 x 35+1 x 16 3 x 50+1 x 25 3 x 70+1 x 35 3 x 95+1 x 50 3 x 120+1 x 70 3 x 150+1 x 70 3 x 185+1 x 95 3 x 240+1 x 120 | 13 14 17 20 23 26 29 34 39 42 47 52 58 | 208.4 251.4 347.8 501.0 702.3 895.7 1211.4 1263.3 2048.9 2070.0 2882.8 3686.5 4604.1 | 7.41/12.4 5.11/7.41 3.08/5.11 1.91/3.08 1.2/1.91 0.87/1.2 0.64/0.87 0.443/0.64 0.320/443 0.253/0.320 0.206/0.253 0.164/0.206 0.125/0.164 |
TECHNICAL SPECIFICATIONS
- Rated operating voltage - 0.6/1.0 kV
- Number of cores - 1,2, 3, 4, 5
- Permissible heating temperature of the cable core during operation: +70°C
- Maximum short circuit temperature: +160?C
- Relative humidity: 98%
- Minimum bending radius 15D (cable outer diameter)
Product code 90087908
brand STP