Cable NYY-LS FE 180 / NYCY-LS FE 180 - STP
general information Cables of this brand are used for transmission and distribution of electricity in the event of a fire (to provide power to fire safety circuits and fire extinguishing pumps, lighting evacuation and emergency exits, evacuation elevators, air ventilation, explosive zones, operating blocks of hospitals). DESIGN Conductor Mica Tape Thermal Barrier PVC insulation with low smoke and gas emission Low fume and gas filling Copper braid or wire shield (for NYCY-LS FE 180) PVC sheath with low smoke and gas emission The design of the cable may vary depending on the duration of fire resistance when exposed to an...general information
Cables of this brand are used for transmission and distribution of electricity in the event of a fire (to provide power to fire safety circuits and fire extinguishing pumps, lighting evacuation and emergency exits, evacuation elevators, air ventilation, explosive zones, operating blocks of hospitals).
DESIGN
- Conductor
- Mica Tape Thermal Barrier
- PVC insulation with low smoke and gas emission
- Low fume and gas filling
- Copper braid or wire shield (for NYCY-LS FE 180)
- PVC sheath with low smoke and gas emission
The design of the cable may vary depending on the duration of fire resistance when exposed to an open flame.
Core manufacturing
Type of conductive cores according to the number of wires forming them | Section, mm2 |
single wire | 1.5 / 10 / - |
stranded | 16 / 240 / 25 / 185 |
Cable specifications
Cable brand | Conductor cross section, mm2 | Maximum electrical resistance of the conductive core at 20°С, Ohm/km, no more |
NYY-LS FE 180 | 3x16 3x25 3x35 3x50 3x70 3x95 3 x 120 3 x 150 3 x 185 3 x 240 4x16 4x25 4x35 4x50 4x70 4x95 4 x 120 4 x 150 4 x 185 4 x 240 5x16 5x25 5x35 3x25+1x16 3x35+1x16 3x50+1x25 3x70+1x35 3x95+1x50 3x120+1x70 3x150+1x70 3x185+1x95 3x240+1x120 | 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 1.15 0.727 0.524 0.727/1.15 0.524/1.15 0.379/0.727 0.268/0.524 0.193/0.379 0.153/0.268 0.124/0.268 0.0991/0.193 0.0754/0.153 |
STP Cable Factory produces low voltage power cables and other sizes
TECHNICAL SPECIFICATIONS
- Fire resistance time when exposed to an open flame: up to 90 / 180 minutes
- Maximum flame temperature: 1000°C
- Rated operating voltage - 0.66/1.0 kV
- Number of cores: 1,2, 3, 4, 5
- Cable operating temperature: -30°C +50°C
- Relative humidity: 98%
- Service life: 30 years
Product code 90087987
brand STP