M wires (ACC) - STP
general information M-type wire (ACC) is used for transmission of electricity over air networks in areas with any climatic conditions related to atmosphere types II and III specified in GOST 15150, or on sea coasts. All wires are twisted in layers, the twist direction of the last layer is right (Z) Twisting direction - right (Z) DESIGN Stranded copper wire conductor Wire Specifications Wire brand Conductor cross section, mm2 Estimated wire weight, kg/km Maximum electrical resistance of the conductive core at 20°С, Ohm/km, no more M (ASS) 6 25 35 50 70 95 120 150 185 240 300 400 142...general information
M-type wire (ACC) is used for transmission of electricity over air networks in areas with any climatic conditions related to atmosphere types II and III specified in GOST 15150, or on sea coasts.
All wires are twisted in layers, the twist direction of the last layer is right (Z)
Twisting direction - right (Z)
DESIGN
Stranded copper wire conductor
Wire Specifications
Wire brand | Conductor cross section, mm2 | Estimated wire weight, kg/km | Maximum electrical resistance of the conductive core at 20°С, Ohm/km, no more |
M (ASS) | 6 25 35 50 70 95 120 150 185 240 300 400 | 142 223 310 443 612 850 1058 1340 1658 2123 2612 3526 | 1.1573 0.7336 0.5238 0.3688 0.2723 0.1944 0.1560 0.1238 0.1001 0.0789 0.0637 0.0471 |
At the STP Cable Plant, bare power wires and other sizes are produced.
TECHNICAL SPECIFICATIONS
- Maximum permitted operating temperature: +90°C
- Service life: 45 years
- Warranty period of the wire from the date of commissioning: 4 years
Product code 90088581
brand РФ