AC wires (ACR) - STP
general information Wire brand AC (ACR) is used for distribution of electricity through overhead networks in climatic conditions related to the atmosphere of types I and II specified in GOST 15150. Wire brand AC (ACR) is used to distribute electricity over air networks in climatic conditions related to the atmosphere of types I and II specified in GOST 15150. Wires of brands ACK, ACKC (ACSR), ACKП (ACSS) are used on sea coasts and salty coasts lakes, in industrial cities and districts, on salt marshes, as well as in places with an atmosphere of types II and III. DESIGN aluminum wires Galvanized steel wire core The...general information
Wire brand AC (ACR) is used for distribution of electricity through overhead networks in climatic conditions related to the atmosphere of types I and II specified in GOST 15150.
Wire brand AC (ACR) is used to distribute electricity over air networks in climatic conditions related to the atmosphere of types I and II specified in GOST 15150. Wires of brands ACK, ACKC (ACSR), ACKП (ACSS) are used on sea coasts and salty coasts lakes, in industrial cities and districts, on salt marshes, as well as in places with an atmosphere of types II and III.
DESIGN
- aluminum wires
- Galvanized steel wire core
The difference between ACK brand wire and AC brand wire is the presence of a heat-resistant neutral lubricant that protects the steel core from heating, and 1 or 2 layers of PET tape wrapping.
The difference between ACKC wire and ACK wire is the presence of a heat-resistant neutral lubricant that protects against heat caused by the PET tape wrap.
The difference between the ACKP brand wire and other wires is the presence of a heat-resistant neutral lubricant on the outer layer, which protects against external heating and heating of other layers.
Wire Specifications
Wire brand | Conductor cross section, mm2 | Breaking strength of the wire, N, not less than | Estimated wire weight, kg/km | Maximum electrical resistance of the conductive core at 20°С, Ohm/km, no more |
AC (ACR) | 10/1.8 16/2.7 25/4.2 35/6.2 40/6.7 50/8.0 63/10.5 70/11 70/72 95/16 95/141 100/16.7 120/19 120/27 125/20.4 150/19 150/24 150/34 160/8.9 160/26.1 185/24 185/29 185/43 185/128 200/11.1 200/32.6 205/27 240/32 240/39 240/56 300/39 300/48 300/66 300/67 300/204 315/21.8 315/51.3 330/30 330/43 400/27.7 400/51.9 400/18 400/22 400/51 400/64 400/93 450/31.1 450/56 500/34.6 500/64.8 500/26 500/27 500/64 550/71 560/38.7 560/70.9 600/72 630/43.6 630.79.8 710/49.1 710/89.9 800/34.6 800/66.7 800/101.3 900/38.9 900/75 1000/43.2 1000/56 1120/47.3 1120/91.2 1250/53.8 1250/101.8 | 4089 62.20 9296 13524 14400 17112 21630 24130 96826 33369 180775 34333 41521 49465 45694 46307 52279 62643 36178 57689 58075 62055 77767 183816 44222 70134 63740 75050 80895 98253 90574 100623 117520 126270 284579 79030 106834 88848 103784 98356 123037 85600 95115 120481 129183 173715 107467 131370 119407 153.796 112548 112188 148257 166164 133736 172592 183835 150453 191772 169559 216124 167407 205433 243520 188333 226500 209259 224047 23428 283168 261750 316036 | 42.6 64.8 100.2 148.5 160.4 194.0 253.7 273.5 755.6 383.5 1356.5 402.5 472.1 523.3 502.7 555.3 600.9 675.7 508.3 646.6 706.2 728.4 847.6 1522.7 636.5 806.5 775.0 922.3 954.0 1107.1 1134.9 1188.7 1313.4 1325.0 2424.8 1042.6 1271.2 1151.8 1255.4 1317.3 1509.2 1199.7 1260.3 1489.6 1574.3 1852.3 1487.1 1639.7 1650.3 1883.9 1593.1 1537.1 1851.1 2075.3 1847.5 2099.1 2169.5 2077.1 2360.1 2342.7 2661.3 2477.6 2733.1 3002.8 2789.1 3072.9 3103.6 3210.1 3461.4 3814.3 3871.3 3871.3 | 2.7064 1.7818 1.1521 0.7774 0.7172 0.5951 0.4553 0.4218 0.4194 0.3007 0.3146 0.2868 0.2440 0.2531 0.2308 0.2046 0.2039 0.2061 0.1800 0.1803 0.1540 0.1591 0.1559 0.1543 0.1440 0.1442 0.1407 0.1182 0.1222 0.1197 0.0958 0.0978 0.1000 0.1000 0.0968 0.0917 0.0916 0.0861 0.0869 0.0722 0.0722 0.0758 0.0733 0.0733 0.0741 0.0711 0.0646 0.0666 0.0577 0.0578 0.0575 0.0600 0.0588 0.0526 0.0515 0.0516 0.0498 0.0458 0.0459 0.0406 0.0407 0.0361 0.0361 0.0361 0.0321 0.0321 0.0289 0.0288 0.0258 0.0253 0.0231 0.0231 |
TECHNICAL SPECIFICATIONS
- Maximum permitted operating temperature: +90°C
- Service life: AC - 45 years, ACK and ACKC - 10 years, ACKP - 25 years
- Warranty period of the wire from the date of commissioning: 4 years
Product code 90088591
brand РФ