Cable KVVG (NYY) - STP
general information Control cables of these brands are used in stationary electrical devices, in AC devices with a rated voltage of 660V or in DC power distribution devices with a rated voltage of up to 1000V, in closed places, in channels and tunnels, in aggressive climatic conditions, in places not exposed to external mechanical impact. KVVG (NYY) / KVVGng (NYY-fl) / KVVGng–LS (NYY-LS) / AKVVG(NAYY) / AKVVGng (NAYY-fl) / AKVVGng – LS (NAYY-LS) Control cables of these brands are used in stationary electrical devices, in AC devices with a rated voltage of 660V or in DC power distribution devices with a rated voltage of up to 1000V,...general information
Control cables of these brands are used in stationary electrical devices, in AC devices with a rated voltage of 660V or in DC power distribution devices with a rated voltage of up to 1000V, in closed places, in channels and tunnels, in aggressive climatic conditions, in places not exposed to external mechanical impact.
KVVG (NYY) / KVVGng (NYY-fl) / KVVGng–LS (NYY-LS) / AKVVG(NAYY) / AKVVGng (NAYY-fl) / AKVVGng – LS (NAYY-LS)
Control cables of these brands are used in stationary electrical devices, in AC devices with a rated voltage of 660V or in DC power distribution devices with a rated voltage of up to 1000V, in closed places, in channels and tunnels, in aggressive climatic conditions, in places not exposed to external mechanical impact. The cores forming the cable are twisted in layers. The two strands in each layer must differ in color from each other and the other strands, or be numbered.
DESIGN
- Conductor made of copper or aluminum wires
- PVC insulation or flame retardant PVC with low fume and gas emission
- Belt insulation made of PET tape
- PVC sheath or flame retardant PVC with low fume and gas emission
Cable specifications
Wire brand | Conductor cross section, mm2 | Estimated wire weight, kg/km | Maximum electrical resistance of the conductive core at 20°С, Ohm/km, no more |
KBBG (NYY) | 4 x 1.0 5 x 1.0 7 x 1.0 10 x 1.0 14 x 1.0 19 x 1.0 27 x 1.0 37 x 1.0 | 85.3 112.5 142.0 196.0 255.1 329.2 451.7 610.7 | 18.10 |
4 x 1.5 5 x 1.5 7 x 1.5 10 x 1.5 14 x 1.5 19x1.5 27 x 1.5 37 x 1.5 | 118.0 141.7 182.7 253.4 332.2 432.3 612.0 809.3 | 12.10 | |
4x2.5 5x2.5 7x2.5 10x2.5 14x2.5 19x2.5 27x2.5 37x2.5 | 164.3 197.6 259.0 362.1 481.4 632.4 896.7 1214.5 | 7.41 | |
4x4.0 7x4.0 10x4.0 | 238.1 383.1 538.1 | 4.61 | |
4x6.0 7 x 6.0 10x6.0 | 323.5 528.3 761.1 | 3.08 |
TECHNICAL SPECIFICATIONS
- Rated operating voltage: 660V
- Conductor cross section, mm2: 0.75, 1.0, 1.5, 2.5, 4.0, 6.0, 10.0
- Number of cores: 2 to 61
- Relative humidity: 98%
- Cable operating temperature: -50°C +50°C
- Service life: underground and on overpasses - 15 years, in closed places, in channels and tunnels - 25 years
Product code 90088601
brand РФ