as@emakgroup.ae

Working hours of the company:

MON - FRI: from 9:00 to 18:00

Order a call
Close
Article number: ENRGSKN-95

PHG 70 TD/PD Cable testing and diagnostic system - BAUR

System for testing 6-35 kV cables with cross-linked polyethylene insulation with variable frequency voltage 0.1 Hz (VLF) with the ability to measure dielectric loss tangent (TD) and partial discharges (PD).

The multifunctional cable testing and diagnostic system PHG 70 TD/PD manufactured by BAUR (Austria) is designed for:

  • Testing of 6-35 kV cables with cross-linked polyethylene insulation with alternating voltage with a frequency of 0.1 Hz (VLF);
  • Testing of power cables with impregnated paper insulation 6-10 kV;
  • Testing the sheath of cables with XLPE insulation;
  • Diagnostics of cables by measuring the dielectric loss tangent (Tan D / TD)
  • Diagnostics of cables by measuring and localizing partial discharges (PD / PD)

PHG TD/PD is a comprehensive system that allows testing at 0.1 Hz/DC and comprehensive diagnostics of the condition of cables and their service life. The combination of two methods: measuring the dielectric loss tangent (dielectric loss coefficient) and measuring partial discharges with their localization - ideally complement each other and allow, on the one hand, to detect complex defects and determine the general condition of the cable line, and on the other hand, to localize the location of the defect in insulation and cable fittings.

Using the MWT (Full Monitored Withstand Test) mode allows you to reduce cable testing time by simultaneously measuring loss tangent and/or partial discharges, thereby reducing the time stress on the cable with increased voltage. Also, comprehensive tests significantly reduce the time for testing and diagnosing a cable line when compared with individual tests using three methods.

Peculiarities:

  • Compliance with foreign and domestic standards in the field of partial discharge measurement (GOST R 55191-2012 / IEC 60270:2000);
  • Manual or fully automatic testing according to standards
  • Automatic condition assessment system with a detailed report
  • High accuracy and sensitivity of PD measurement
  • Comprehensive MWT Test
  • Possibility of integration into ETL

Technical characteristics of the PHG 70 TD / PD BAUR :

Output voltage

AC sine voltage (0.1 Hz)

0-38 kV (rms) / 1.4 – 53.7 kV (peak)

Variable voltage-square wave (0.1 Hz)

1-57 kV

Rectified voltage

+/– 70 kV

Permission

0.1 kV

Accuracy

1%

Frequency range

0.01 - 1 Hz

Maximum capacitive load

Up to 20 µF

3 µF at 0.1 Hz / 38 kV (rms)

4 µF at 0.1 Hz / 30 kV (rms)

Output current

Output current

10 mA at 70 kV (DC)

60 mA at 50 kV (DC)

90 mA at 20 kV (DC)

Range

0-120 mA

Permission

10 µA

Accuracy

1%

Dielectric loss tangent measurement

AC voltage - sine (0.1 Hz)

1-38 kV (rms)

Measurement frequency

0.1 Hz

Load range

>10 nF

Measuring range

1 x 10-3 / 1000 x 10-3

Measurement accuracy tan D

1 x 10-4

Permission

1 x 10-6

Registration of leakage currents

VSE-Box option

Partial discharge measurement

AC voltage - sine (0.1 Hz)

1-38 kV (rms)

Cable length limits

10-12800 m (at V/2 = 80 m/µs)

Wave propagation speed

50-120 m/µs

Sampling frequency

100 Msamples (10 ns)

Localization accuracy

1% of cable length

Permission

0.1 pC / 0.1 m

Total information

Display

TFT monitor, 15.1"

User Interface Languages

Russian, English, Arabic, Chinese (China), Chinese (Taiwan), Danish, German, Finnish, French, Greek, Italian, Korean, Malay, Dutch, Norwegian, Polish, Portuguese, Romanian, Serbian, Swedish, Spanish, Czech

Nutrition

200–260 V, 50/60 Hz

Max. power consumption

3,500 VA

Ambient temperature (high voltage generator)

-20 to +55 °C

Storage temperature (high voltage generator)

-30 to +70 °C

Dimensions (W x H x D) (High Voltage Generator)

approx. 483 x 623 x 775 mm

Weight:

High voltage generator

General

approx. 160 kg

from 250 kg (depending on configuration)

Basic equipment of PHG 70 TD/PD:

  • High voltage generator PHG 70
  • Built-in loss tangent TD measurement module
  • Module for measuring and localizing partial discharges PD
  • Industrial PC with installed software: Windows 7 Ultimate and BAUR system software, without monitor
  • TFT monitor, 15.1"
  • Computer keyboard
  • Control unit with safety device SCU
  • Discharge device DU 80
  • Cable drum rack KTG M3 with high-voltage connecting cable, mains cable and earth cable, each 25 m
  • Connection kit including G-clamp and anti-corona protection
  • Kit for connecting a VSE device (VSE-Box) for measuring dielectric loss factor
  • Ground rod GR 80
  • 19" rack for PHG 70 TD PD
  • Manual
  • Warranty card of Energoscan Group of Companies

Guarantee period 1 год