RCDT310 RCD parameter meter - Megger
Three-phase testing of all types of RCDs, because standard, direct current and selective. Currents are 30 mA, 100 mA, 300 mA and 500 mA. Voltage measurement up to 300V, frequency measurement up to 450Hz. VERIFICATION - 1600 rubles.The RCDT 310 RCD parameter meter manufactured by M egger (England) is intended for three-phase testing of all types of RCDs, because standard, direct current and selective (with time delay) rated 30 mA, 100 mA, 300 mA and 500 mA. Testing is carried out with current: 1/2I, 1xI and 5xI in position 0? and 180. Test time for conventional/selective devices: 1/2 I -2s/2s, I - 300ms/2s, 5 I -40ms/150ms
At the start of RCD testing, RCDT 310 measures the touch voltage and if this voltage exceeds the set level, testing will be automatically disabled. Touch voltage is selectable 25 V or 50 V.
The RCDT 310 meter is designed in a shockproof and rubber-reinforced housing. A durable cover protects the display during transport and closes it when testing is complete. IP54 design allows the devices to be used in any weather
The RCDT 310 device measures voltage up to 300V, and also allows you to measure frequency in the range from 25Hz to 450Hz.
The device is powered by 8x1.5 V AA batteries or 8x1.2 V batteries. The power supply charge is enough for 2000 tests.
The design of the RCDT 310 M egger ensures exceptional safety of use. The instrument has LED connection indicators that indicate test lead connections and power status. If the supply voltage exceeds 280V, the test will be prohibited.
Functional features of RCDT 310:
- 30 mA, 100 mA, 300 mA and 500 mA current testing
- Touch voltage
- Frequency measurement from 25Hz to 450Hz
- IP54 shockproof housing
- High security
Guarantee period 3 года