RCDT330 RCD parameter meter - Megger
Three-phase testing of all types of RCDs, because standard, direct current and selective. Currents 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000 mA. Voltage measurement up to 300V, frequency measurement up to 450Hz. Automatic testing. Internal memory. Data transfer to PC. VERIFICATION - 1600 rubles.The RCDT 330 RCD parameter meter, manufactured by M egger (England), is intended for three-phase testing of all types of RCDs, because standard, direct current and selective (with response time delay) rated 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000 mA. Testing is carried out with current: 1/2I, 1xI and 5xI in position 0? and 180. Test time for conventional/selective devices: 1/2 I -2s/2s, I - 300ms/2s, 5 I -40ms/150ms
At the start of RCD testing, RCDT 330 measures the touch voltage and if this voltage exceeds the set level, testing will be automatically disabled. Touch voltage is selectable 25 V or 50 V.
The RCDT 330 meter is designed in a shockproof and rubber-reinforced housing. A durable cover protects the display during transport and closes it when testing is complete. IP54 design allows the devices to be used in any weather
RCDT 330 tests the actual breaking current . To measure the tripping current of the RCD, the current level slowly increases from 1/2I to 1I (+10%). When the RCD trips, the tripping current appears on the screen and is held.
The automatic testing function of RCD 330 allows you, when the RCD is located at a distance from the device connection point, to turn on the test mode and go to the RCD. The device will automatically switch testing modes 1/2I, 1xI and 5xI at 0° and 180°, and the operator remains near the RCD and restores its functionality; when the operator returns to the device, all that remains is to view the test results on the display and in the device memory. Then these and the results can be transferred to a PC via USB port.
The RCDT 330 device measures voltage up to 300V, and also allows you to measure frequency in the range from 25Hz to 450Hz.
The device is powered by 8x1.5 V AA batteries or 8x1.2 V batteries. The power supply charge is enough for 2000 tests.
The design of the RCDT 330 Megger ensures exceptional safety of use. The instrument has LED connection indicators that indicate test lead connections and power status. If the supply voltage exceeds 280V, the test will be prohibited.
Functional features of RCDT 330:
- Current testing 10mA, 30mA, 100mA, 300mA, 500mA, 1000mA.
- Touch voltage
- Frequency measurement from 25Hz to 450Hz
- IP54 shockproof housing
- Trip current testing
- Automatic test mode
- Saving data
- Transfer data to PC
Differences from RCDT3 2 0:
- Saving data
- Transfer data to PC
Guarantee period 3 года