Article number: ENRGSKN-204

REIS-405 Reflectometer - STELL

REIS-405 is a powerful and compact reflectometer manufactured by STELL, designed to determine fault locations in power cable lines. The device is effective when used as part of an electrical laboratory.

REIS-405 is a powerful and compact reflectometer manufactured by STELL, designed to determine fault locations in power cable lines. The device is effective when used as part of an electrical laboratory.

Functional features of REIS-405:

  • The device is made in the form of a monoblock and combines the capabilities of 4 measuring instruments, including a reflectometer for metal cable and overhead lines, an insulation resistance meter, a meter using the pulse-arc method and a meter using the oscillatory discharge method.
  • The device is equipped with a wide color display. You can also connect an external display of any size to the device for ease of control.
  • A powerful probing signal and an increased measurement range expand the possibilities of using the device.
  • Convenience of testing is ensured by a simple and intuitive interface of the device and direct control of measurement parameters.
  • Compact size, light weight and convenient location of controls and connections
  • Suitable for stand-alone use and as part of electrical measuring laboratories for detecting, identifying and determining the distance to defects in power cable lines and other types of lines with metal conductors.

Technical characteristics of the computer reflectometer REIS-405:

Parameter Meaning
"REFLECTOMETER METHOD" mode
Ranges of measured distances (with a shortening factor of 1.5) minimum range is 250 m
maximum range - 250000 m
Shortening factor setting or measuring within 1.00...7.00
embedded table
Probing signals amplitude 25 V...120 V
duration from 30 ns to 300 µs
Output impedance 10...1000 Ohm, software-adjustable, with value displayed on the screen
Instrumental distance measurement error no more than 0.1%
Distance reference system using vertical cursors
Measurement Modes Straight reading and displaying the current reflectogram from any of the inputs: input L1; input L2, input L3
Comparison superposition of two or three reflectograms (input-input, input-memory, memory-memory, inputs L1-L2-L3)
Separated probing via input L1 and receiving via inputs L2 or L3 (L1-L2, L1-L3)
Difference displaying the result of the difference between two reflectograms (input-input, input-memory, memory-memory
Stretching possibility of stretching a selected area of the reflectogram
Memory ability to store more than 1000 reflectograms and impulse characteristics in the built-in non-volatile memory
Rejection of additive interference and noise averaging via digital accumulation, signal filtering
Synchronous noise rejection when reading reflectograms - through the use of comparison and difference modes of reflectograms of serviceable and faulty lines (cable cores)
during digital processing of reflectograms from memory - through the use of comparison and difference modes of reflectograms of a line from memory and reflectograms of faulty lines (cable cores)
Information display reflectograms and processing results are displayed graphically on a 10.4'' color TFT screen
modes, parameters and information - in alphanumeric and symbolic form
Nutrition AC mains 100...240 V, 50...60 Hz
DC 12V
terms of Use 0...+50 °С
Dimensions (WxHxD) 270 x 300 x 122 mm
Weight no more than 7.5 kg
Mode "OSCIBLE DISCHARGE METHOD"
Ranges of measured distances (with a shortening factor of 1.5) minimum range – 250 m
maximum range – 250000 m
Maximum amplitude of input signals 50 V
Input impedance by wave input 300 Ohm
Instrumental distance measurement error no more than 0.1%
Gain –18 to +74 dB
Operating modes view line
waiting for discharge
autostart (with the ability to automatically save impulse responses in memory)
Sampling frequency 200 MHz
Connection to the line (using the oscillatory discharge method) via voltage or current connection device
"PULSE-ARC METHOD" mode
Ranges of measured distances (with a shortening factor of 1.5) minimum range – 250 m
maximum range – 250000 m
Amplitude range of input signals (periodic and single) at the input 0.002 … 120 V (without voltage connection device)
Instrumental distance measurement error no more than 0.1%
Gain –18 to +74 dB
Operating modes view line
waiting for discharge
autostart (with the possibility of automatic reflectograms in memory)
two synchronization sources: internal and external (the synchronization signal is received at the corresponding input)
Sampling frequency 200 MHz

Delivery set REIS-405:

  • Computer reflectometer REIS-405 1
  • Connecting cable 3
  • Connecting cable, 2 meters 3
  • Connecting cable, 3 meters 3
  • Tee (for verification) 1
  • Load (for verification) 1
  • Network adapter 1
  • Case (for carrying) 1
  • Instruction Manual 1
  • Form 1

Guarantee period 1 год