The STS-4000 TD system is designed for inspection and electrical testing of power transformers, current transformers, voltage transformers, high-voltage circuit breakers, generators, grounding devices and other primary and secondary equipment. The high automation of the STS-4000 device allows you to speed up the testing process and reduce the number of possible errors. Combining the STS-4000 device with additional modules can significantly expand the functionality of the system.STS-4000 TD - a comprehensive testing system for substation equipment manufactured by ISA (Italy) is designed to conduct automatic comprehensive electromagnetic and dielectric tests of power transformers, current transformers (CT) and voltage transformers (VT). The device also allows you to conduct a number of tests of high-voltage switches, relay protection devices, grounding devices and overhead lines.
The difference between the STS-4000 system and the STS-5000 is the absence in the STS-4000 of high-current outputs of 800 A alternating current and 400 A direct current, and, accordingly, the impossibility of conducting a number of CT and VT tests without these outputs.
The operator is required to assemble a measurement scheme, enter the parameters of the test object, tolerances, select the required test and press the test start button. The device automatically carries out the test, generating and measuring all the necessary quantities and recording the results in memory. Test results are stored in local memory and can be transferred to a PC for storage, analysis and report generation.
The STS-4000 device is controlled in two ways:
- without PC: via own controls and large color LCD display,
- using a PC and TDMS software.
TD-5000 is a module used in conjunction with the STS-5000 device to measure the dielectric loss tangent and capacitance of transformers. The module generates voltage up to 12 kV with the ability to change the generation frequency from 1 to 500 Hz. Both units and cables are mounted on a trolley for ease of transportation. The use of unique circuit designs and the ability to test at frequencies other than 50 Hz ensure high accuracy measurements even in the most difficult electromagnetic conditions.
Power transformers | -Transformation coefficient, - Ohmic resistance of the windings (including recording resistance in dynamic mode when switching the on-load tap-changer) - No-load current | - Short circuit resistance -Demagnetization of the magnetic circuit - Determination of the circuit and group of winding connections - Measurement of dielectric loss tangent and capacitance |
Current transformers | - Transformation ratio (current method), only with BUX option; - Transformation ratio (voltage method) - Secondary side load resistance - Magnetization characteristic | - Winding resistance, - High voltage test of secondary circuits - Measurement of dielectric loss tangent and capacitance |
Voltage transformers | - Transformation ratio, polarity - Secondary side load resistance, - Transformation ratio of electronic transformers | - High voltage test - Measurement of dielectric loss tangent and capacitance |
High voltage circuit breakers | - Measurement of dielectric loss tangent and capacitance | |
Generators and engines | - Measurement of dielectric loss tangent and capacitance of objects with high capacitance | |
Grounding devices | - Ground resistance and soil resistivity | - Step voltage and ground voltage |
Air Lines | - Impedance measurement to calculate distance protection relay settings |
OPTIONAL EQUIPMENT:
STCS / STCS Plus -Switch | The switch allows the STS 5000 to conduct electromagnetic tests in automatic mode: - STCS: transformation ratio, ohmic resistance of windings, short-circuit resistance, XX current at voltages up to 300 V - STCS Plus: transformation ratio, XX current, ohmic resistance of windings, short-circuit resistance, demagnetization at voltages up to 400 V. Measurements are taken on all three phases of the low and high side of the power transformer. During testing, repeated climbs of personnel onto the transformer for recommutations are not required. Also, the STCS switch can control the operation of the on-load tap-changer and make checks on all branches. |
STDE – Degaussing module | The module allows you to demagnetize the magnetic circuit to obtain the correct results of the XX experiment or to measure the frequency response (FRA) |
20 A DC STCS – Current amplifier | The module allows you to measure the resistance of transformer windings using a STCS/STCS Plus switch with a direct current of up to 20 A |
Kit "Grounding" | The kit is a set of accessories for measuring grounding resistance and soil resistivity. |
Set “Step and Touch Tension” | The kit is a set of accessories for measuring ground resistance, soil resistivity and touch and step voltage. |
Line Impedance Kit | The kit is a set of accessories for measuring line impedance. |
PLCK – Polarity Measuring Module | The module is designed to measure the polarity of the load connection of secondary circuits of CT and VT. |
BUX 2000/3000/5000-AC load transformer | The BUX AC load transformer allows the STS-5000 to perform primary current testing up to 2000/3000/7000 A. The transformer generates high current at low voltage and transmits the measured data to the STS5000. |
STOIL - Oil Loss Tangent Cell | The cell allows you to measure the dielectric loss tangent of liquid dielectrics, such as transformer oil. The cell is connected to the TD-5000 unit, the results are transmitted to the STS-5000. |
RCDT – Compensating Reactor | Compensating reactor module for measuring dielectric loss tangent and capacitance of rotating machines |
High voltage AC output
Output voltage | 2000 V |
Max. power | 2500 W |
Measurement error | < (0.05% reading + 0.05% span) typical |
Low current AC output
Output current | 6 A / 3 A |
Output voltage | 70 V / 140 V |
Max. power | 360 VA |
Low current DC output
Output current | 6 A |
Output voltage | 65 V |
Max. power | 360 W |
Low voltage AC output
Output current | 140 V / 70 V |
Max. power | 420 VA |
Common to current and voltage outputs
Frequency range | 15 … 500 Hz |
Frequency resolution | 10 m Hz |
Measuring inputs
AC input | 10 A < (0.05% of reading + 0.05% of range) |
DC input | 10 A < (0.03% of reading + 0.08% of range) |
AC input 1 | 300 V < (0.05% of reading + 0.05% of range) |
AC input 2 | 3 V < (0.03% of reading + 0.08% of range) |
DC input | 10 V < (0.03% of reading + 0.08% of range) |
Phase angle measurement
Range | 0 – 360° |
Permission | 0.01° |
Error | <0.1° |
Discrete input
Digital inputs (quantity) | 1 |
Contact options | "dry"; live (AC, DC) |
Time measurement resolution | 1 ms |
Display
Type | TFT LCD Color |
Permission | 640 x 480 |
Display size | 132 x 99 mm |
Communication Interfaces
Ethernet | Eat |
USB for PC connection | Eat |
USB for connecting a USB flash drive | 2 pcs |
Dimensions and weight
dimensions | 450 x 400 x230 mm |
Weight | 29 kg |
Temperature Range
Storage temperature | -20 … 70° C |
Working temperature | -10 … 55° C |
Dielectric loss tangent measurement
Module name | TD 5000 |
Maximum voltage | 12000 V |
Maximum output current | 300 mA |
Frequency | 1…500 Hz |
Impedance measurement | 1 kOhm – 1400 MOhm (0.5% of measured value) |
Power measurement | 10 kW/100 kV/1 MV (0.5% of reading + 1 mW) |
Dimensions | 440 x 345 x210 mm |
Weight | 25 kg |
Capacitance measurement (range/accuracy)
Range 1 | 1 pF – 5 µF ± (0.1% of reading + 0.1 pF) |
Range 2 | 5 µF – 200 µF ± (0.5% of reading + 1 nF) |
Loss tangent measurement
Range 1 | 0 - 10% (0.1% of measured value + 0.005%) |
Range 2 | 0% - 100% (0.5% of measured value + 0.02%) |
Range 3 | >100% (0.8% of measured value + 0.05%) |
Inductance measurement
Range 1 | 1 Hn – 10 kHn (0.5% of measured value) |
Range 2 | 100 Gn – 1 MGn (0.5% of measured value) |
- Universal system STS-4000
- Tan D and Capacitance Measurement Module TD-5000
- Cable kit
- Cart
- Universal software
- Transport case
- Transport case for cables
- Manual
- Certificate of initial verification
- Warranty card of Energoscan Group of Companies
Additional equipment
- STCS Switch
- STCS Plus Switch
- STDE degaussing module
- Cell for measuring tan D of liquid dielectrics
- Kit "Grounding"
- Touch and Step Voltage Kit
- Line Impedance Kit
- Digital temperature and humidity sensor
- Flashing Light
- External test enable button
- Calibration module TD-5000
- Clamp meter
- Load transformer BUX 2000/3000/5000
- PADS – program for controlling the device from a PC (3 versions)
- Amplifier 20 A DC STCS
Guarantee period 1 год