STS-5000 Device for comprehensive testing of transformers and substation equipment - I.S.A. - Altanova group

The STS-5000 is designed for testing power transformers, current transformers, voltage transformers, high-voltage circuit breakers, generators, grounding devices and other primary and secondary electrical equipment. The high automation of the STS-5000 device allows you to speed up the testing process and reduce the number of possible errors.

STS-5000 - a testing complex for testing substation equipment manufactured by ISA (Italy) is designed to conduct automatic comprehensive electromagnetic and dielectric tests of power transformers, current transformers (CT) and voltage transformers (VT). The device also allows you to conduct a number of tests of high-voltage switches, relay protection devices, grounding devices and overhead lines.

The operator is required to assemble a measurement scheme, enter the parameters of the test object, tolerances, select the required test and press the test start button. The device automatically carries out the test, generating and measuring all the necessary quantities and recording the results in memory. Test results are stored in local memory and can be transferred to a PC for storage, analysis and report generation.

The STS-5000 is controlled in two ways: without a PC: through its own controls and large color LCD display, and using a PC and TDMS software.

TD-5000 is a module used in conjunction with the STS-5000 device to measure the dielectric loss tangent and capacitance of transformers. The module generates voltage up to 12 kV with the ability to change the generation frequency from 1 to 500 Hz. Both units and cables are mounted on a trolley for ease of transportation. The use of unique circuit designs and the ability to test at frequencies other than 50 Hz ensure high accuracy measurements even in the most difficult electromagnetic conditions.

Types of tests and measurements

Power transformers:

-Transformation coefficient,

- Ohmic resistance of the windings (including recording resistance in dynamic mode when switching the on-load tap-changer)

- No-load current

- Short circuit resistance

-Demagnetization of the magnetic circuit

- Define connection group

- Measurement of dielectric loss tangent and capacitance.

Current transformers

- Transformation ratio

- Transformation ratio, polarity and load resistance with increased alternating current;

- Secondary side load resistance

- Magnetization characteristics,

- Winding or load resistance,

- High voltage test,

- Polarity check

- Measurement of dielectric loss tangent and capacitance

Voltage transformers

- Transformation ratio, polarity

- Secondary side load resistance,

- Transformation ratio of electronic transformers

- High voltage test

- Polarity check

- Measurement of dielectric loss tangent and capacitance

High voltage circuit breakers:

- Contact resistance

- Measurement of dielectric loss tangent and capacitance

Generators and engines

- Measurement of dielectric loss tangent and capacitance of objects with high capacitance

Overcurrent protection

Response times of circuit breakers and relay protection devices

Grounding devices

- Ground resistance and soil resistivity

Step voltage and soil stress

Air Lines

Impedance measurements to calculate distance protection relay settings

High Current AC Output

Output current 800 A
Max. power 4800 VA
Measurement error < (0.1% of reading + 0.1% of range)
Maximum current with optional BUX module 2000 A / 3000 A / 7000 A


High Current DC Output

Output current 400 A
Max. power 2600 W
Measurement error < (0.2% of reading + 0.05% of range)


High voltage AC output

Output voltage 2000 V
Max. power 2500 W
Measurement error

< (0.05% reading + 0.05% span) typical


Low current AC output

Output current 6 A / 3 A
Output voltage 70 V / 140 V
Max. power 360 VA


Low current DC output

Output current 6 A
Output voltage 65 V
Max. power 360 W


Low voltage AC output

Output current 140 V / 70 V
Max. power 420 VA


Common to current and voltage outputs

Frequency range 15 … 500 Hz
Frequency resolution 10 m Hz


Measuring inputs

AC input 10 A < (0.05% of reading + 0.05% of range)
DC input 10 A < (0.03% of reading + 0.08% of range)
AC input 1 300 V < (0.05% of reading + 0.05% of range)
AC input 2

3 V < (0.03% of reading + 0.08% of range)

DC input 10 V < (0.03% of reading + 0.08% of range)


Phase angle measurement

Range 0 – 360°
Permission 0.01°
Error <0.1°


Discrete input

Digital inputs (quantity) 1
Contact options "dry"; live (AC, DC)
Time measurement resolution 1 ms


Display

Type TFT LCD Color
Permission 640 x 480
Display size 132 x 99 mm


Communication Interfaces

Ethernet Eat
USB for PC connection Eat
USB for connecting a USB flash drive 2 pcs


Dimensions and weight

dimensions 450 x 400 x 230 mm
Weight 29 kg


Temperature Range

Storage temperature -20 … 70° C
Working temperature -10 … 55° C


Dielectric loss tangent measurement

Module name TD 5000
Maximum voltage 12000 V
Maximum output current 300 mA
Frequency 1…500 Hz
Impedance measurement 1 kOhm – 1400 MOhm
(0.5% of measured value)
Power measurement 10 kW/100 kV/1 MV
(0.5% of reading + 1 mW)
Dimensions 440 x 345 x210 mm
Weight 25 kg


Capacitance measurement (range/accuracy)

Range 1 1 pF – 5 µF
± (0.1% of reading + 0.1 pF)
Range 2 5 µF – 200 µF
± (0.5% of reading + 1 nF)


Loss tangent measurement

Range 1 0 - 10%
(0.1% of measured value + 0.005%)
Range 2 0% - 100%
(0.5% of measured value + 0.02%)
Range 3 >100%
(0.8% of measured value + 0.05%)


Inductance measurement

Range 1 1 Hn – 10 kHn
(0.5% of measured value)
Range 2 100 Gn – 1 MGn
(0.5% of measured value)
Standard equipment:
  • Universal system STS-5000
  • Tan D and Capacitance Measurement Module TD-5000
  • Cable kit
  • Cart
  • Universal software
  • Transport case
  • Transport case for cables
  • Manual
  • Certificate of initial verification
  • Warranty card of Energoscan Group of Companies

Additional equipment:

  • Three-phase switch STCS
  • Three-phase switch STCS Plus
  • STDE degaussing module
  • RCDT – Compensating Reactor
  • Cell for measuring tan D of liquid dielectrics
  • Kit "Grounding"
  • Touch and Step Voltage Kit
  • Line Impedance Kit
  • Digital temperature and humidity sensor
  • Flashing Light
  • External test enable button
  • Calibration module TD-5000
  • Clamp meter
  • Load transformer BUX 2000/3000/5000
  • PADS – instrument control program from a PC (3 versions)

Guarantee period 1 год