as@emakgroup.ae

Working hours of the company:

MON - FRI: from 9:00 to 18:00

Order a call
Close
Article number: ENRGSKN-230

TD-5000 Dielectric tangent and capacitance measurement module - I.S.A. - Altanova group

The module is an option for STS 5000/4000 systems and is designed to measure the dielectric loss tangent and capacitance of transformers and other electrical equipment at voltages up to 12 kV. Testing is automated as much as possible to speed up the testing process and reduce possible errors. High noise immunity.

The module for measuring the dielectric loss tangent and capacitance, manufactured by ISA (Italy), is intended for diagnosing the insulation of transformers and other electrical equipment together with the STS 5000 or STS 4000 system.

High voltage is completely isolated from live parts and the housing, and accordingly the device does not require additional insulating supports during measurements. The high-voltage cable supplied with the device is also insulated for voltages up to 15 kV and does not need to be hung on insulating racks.

The TD 5000 module can be used to measure dielectric constant, dielectric loss tangent of transformer oil. To do this, you must use a STOIL oil measuring cell.

The device is made in an aluminum case with handles. For ease of transportation, the device can be installed on a special trolley with large wheels.

Functional features:

  • Fully automatic measurement process
  • Possibility of measuring dielectric loss tangent, capacitance and no-load losses/excitation current.
  • Testing of electric motors and generators
  • Variable frequency: 1- 500 Hz
  • Output voltage up to 12 kV
  • Compact and lightweight
  • Patented loss tangent and capacitance measurement technology

Technical characteristics of TD- 5000:

Characteristics:

Maximum voltage

12000 V

Maximum output current

300 mA

Frequency

1…500 Hz

Capacitance measurement (range/accuracy)

Range 1

Range 2

1 pF – 5 µF

± (0.1% of reading + 0.1 pF)

5 µF – 200 µF

± (0.5% of reading + 1 nF)

Loss tangent measurement

Range 1

Range 2

Range 3

0 - 10%

(0.1% of measured value + 0.005%)

0% - 100%

(0.5% of measured value + 0.02%)

>100%

(0.8% of measured value + 0.05%)

Impedance measurement

1 kOhm – 1400 MOhm

(0.5% of measured value)

Power measurement

10 kW/100 kV/1 MV

(0.5% of reading + 1 mW)

Inductance measurement

Range 1

Range 2

1 Hn – 10 kHn

(0.5% of measured value)

100 Gn – 1 MGn

(0.5% of measured value)

Dimensions and weight

dimensions

440 x 345 x 210 mm

Weight

25 kg

Standard equipment of the TD- 5000 complex:

  • Module TD-5000*
  • Cable set
  • Transport case
  • Transport trolley
  • Transport case for cables
  • Warranty card of Energoscan Group of Companies

*Note: Must be used with STS system