The TDX-5000 system is designed to measure the dielectric loss tangent and capacitance of transformers and other electrical equipment at voltages up to 12 kV. The high-voltage and measuring parts are located in the same housing with a built-in test control unit. High automation of the TDX-5000 device allows you to speed up the testing process and reduce the number of possible errors. High noise immunity.TDX-5000 - dielectric loss tangent and capacitance measurement system manufactured by ISA (Italy) . The device is intended for diagnostics of insulation of transformers and other electrical equipment.
The uniqueness of the TDX-5000 lies in the fact that the control unit, high-voltage and measuring units are located in one housing. High voltage is completely isolated from live parts and the housing, so the device does not require additional insulating supports during measurements. The high-voltage cable supplied with the device is also insulated for voltages up to 15 kV and does not need to be hung on insulating stands.
The TDX-5000 system is fully automatic and is controlled using a display, keypad and multi-function button. Measurement results are saved to internal memory or to a USB flash drive. It is also possible to control the device using PADS software (included in TDMS).
When measuring the insulation loss tangent of high capacitance objects such as motors and generators, the RCDT compensating reactor option is included with the instrument.
The TDX-5000 system can be used to measure the dielectric loss tangent of transformer oil. To do this, you must use a STOIL oil measuring cell.
The device is made in an aluminum case with handles. For ease of transportation, the TDX-5000 can be mounted on a special cart with large wheels.
Functional features of TDX-5000
- Fully automatic measurement process
- Possibility to measure dielectric loss tangent, capacitance and no-load loss/excitation current
- Testing of electric motors and generators
- Variable frequency: 1- 500 Hz
- Output voltage up to 12 kV
- Compact and lightweight
- Patented loss tangent and capacitance measurement technology
- Possibility of control from a PC Communication interfaces USB and Ethernet
Dielectric loss tangent measurement | |
Maximum voltage | 12000 V |
Maximum output current | 300 mA |
Frequency | 1…500 Hz |
Capacitance measurement (range/accuracy) Range 1 Range 2 | 1 pF – 5 µF ± (0.1% of reading + 0.1 pF) 5 µF – 200 µF ± (0.5% of reading + 1 nF) |
Loss tangent measurement Range 1 Range 2 Range 3 | 0 - 10% (0.1% of measured value + 0.005%) 0% - 100% (0.5% of measured value + 0.02%) >100% (0.8% of measured value + 0.05%) |
Impedance measurement | 1 kOhm – 1400 MOhm (0.5% of measured value) |
Power measurement | 10 kW/100 kV/1 MV (0.5% of reading + 1 mW) |
Inductance measurement Range 1 Range 2 | 1 Hn – 10 kHn (0.5% of measured value) 100 Gn – 1 MGn (0.5% of measured value) |
Display | |
Type | TFT LCD Color |
Permission | 640 x 480 |
Display size | 132 x 99 mm |
Communication Interfaces | |
Ethernet | Eat |
USB for PC connection | Eat |
USB for connecting a USB flash drive | 2 pcs |
Temperature Range | |
Storage temperature | - 20 … 70 °C |
Working temperature | -10 … 55 °C |
Dimensions and weight | |
dimensions | 450 x 530 x215 mm |
Weight | 39 kg |
- TDX-5000 system
- Cable set
- Universal TDMS Software
- Transport case
- Transport case for cables
- Manual
- Certificate of initial verification
- Warranty card of Energoscan Group of Companies
Additional equipment TDX-5000
- Tan D Oil Measuring Cell
- Compensating reactor RCDT
- Digital temperature and humidity sensor
- Flashing Light
- External test enable button
- TDX-5000 Calibration Module
- Cart
Guarantee period 1 год